TABLE 44 – MICROBOARD BINARY INPUTS
30VDC UNREGULATED SUPPLY | |
UNIT ON/OFF SWITCH | |
PWM TEMP RESET | |
| OR LOAD LIMIT STAGE 2 ON 3 & 6 COMP UNITS |
LOAD LIMIT STAGE 1 | |
FLOW SWITCH AND REMOTE START / STOP | |
| (SYS 1 ZONE THERMOSTAT - YCUL ONLY) |
|
|
SYSTEM 2 ZONE THERMOSTAT - YCUL ONLY | |
|
|
SINGLE SYSTEM SELECT | |
| (JUMPER = SINGLE SYS, NO JUMPER=TWO |
| SYS) |
|
|
CR1 (SYS 1 MOTOR PROTECTOR / HIGH | |
| PRESS CUTOUT) |
|
|
CR2 (SYS 2 MOTOR PROTECTOR / HIGH | |
| PRESS CUTOUT) |
|
|
TABLE 45 – MICROBOARD ANALOG INPUTS
Sys 1 Suction Press Transducer or | ||
| Sys 1 Low Press Switch | |
SPARE | ||
Sys 1 Discharge Pressure Transducer (optional) | ||
Sys 1 Suction Temp Sensor - YCUL Option | ||
Sys 2 Suction Temp Sensor - YCUL Option | ||
SPARE | ||
SPARE | ||
Ambient Air Temperature Sensor | ||
Leaving Chilled Liquid Temperature Sensor | ||
|
| |
| Return Chilled Liquid Temperature Sensor | |
or | ||
| Discharge Air Temp Sensor - YCUL Only | |
|
| |
Sys 2 Suct Press Transducer | ||
or | ||
| ||
| Sys 2 Low Press Switch | |
SPARE | ||
Sys 2 Discharge Pressure Transducer (optional) | ||
|
| |
Sys 1 Ground Fault Circuit | ||
|
| |
Sys 2 Ground Fault Circuit |
| FORM |
TABLE 46 – MICROBOARD OUTPUTS | |
|
|
SYSTEM 1 COMPRESSOR 1 | |
SYS 1 LIQUID LINE SOLENOID VALVE | |
SYSTEM 1 COMPRESSOR 2 | |
SYSTEM 1 COMPRESSOR 3 | |
SYSTEM 1 HOT GAS BYPASS VALVE | |
SYSTEM 2 COMPRESSOR 1 | |
SYS 2 LIQUID LINE SOLENOID VALVE | |
SYSTEM 2 COMPRESSOR 2 | |
SYSTEM 2 COMPRESSOR 3 | |
SYS 1 CONDENSER FAN STAGE 1 | |
SYS 1 CONDENSER FAN STAGE 2 | |
SYS 1 CONDENSER FAN STAGE 3 | |
SYS 2 CONDENSER FAN STAGE 1 | |
SYS 2 CONDENSER FAN STAGE 2 | |
SYS 2 CONDENSER FAN STAGE 3 | |
EVAPORATOR HEATER | |
SYSTEM 1 ALARM | |
SYSTEM 2 ALARM | |
EVAPORATOR PUMP STARTER |
3
*The 30 dc unregulated supply is not an input. This voltage originates on the microboard and is used to supply the contacts for the binary inputs.