M4557 - Model 9210 Nitriding Controller
IP Address Mask 3 | 255 |
IP Address Mask 4 | 0 |
IP Address Gateway 1 | 192 |
IP Address Gateway 2 | 168 |
IP Address Gateway 3 | 1 |
IP Address Gateway 4 | 1 |
|
|
Highlighting the parameter that needs to be entered and pressing the Enter button displays a numeric keypad that can be used to enter the required value. This will range from 0 to 256.
The default IP address is: 192.168.0.200
The default IP Address Gateway is: 192.168.1.1
Pressing the Esc key returns you to the configuration menu.
Event Control
This menu option will allow the user to set up the event control for the 9210. The “Hold Instrument Number” selection will display a numeric keypad that can range from 0 to 11. The “Hold Minimum PV” selection will display a numeric keypad that will range from 0 to 4000. The “Hold Maximum PV” selection will display a numeric keypad that will range from 0 to 4000. The “Event for Program Run” selection will display a numeric keypad that will range from
selection is:
•Event Inactive
•Event Active, Open Triggers Hold
•Event Active, Closed Triggers Hold
Valve Configuration
This screen provides setup information for the 9210 on the flow controller boards.
The “Decimal Place” selection determines how the 9210 will display gas flows. This will display a numeric keypad that can range from 0 to 4.
The “Valve Control Mode” selection determines how the 9210 will adjust gas flows if required for %Dissociation. This will display a screen that will allow the user to select the mode. The choices are:
•Individual Trim
•Flow
•Ratio
•Auto
The “D.A. Switch Point” selection determines the
control switch point for switching the atmosphere display from %Dissociation to Kn. This will display a
SSi Manual SERIES | Page 32 of 32 |