SSI America 9210 user manual Flow Head Unit, Mass Flow Meters, Gas Solenoids

Page 52

M4557 - Model 9210 Nitriding Controller

ON. The Emergency Nitrogen solenoid is a normally open solenoid and will be open on power failure to the control panel.

Flow Head Unit

The process gas flow system is located below the sampling The flow head unit is divided into the following parts; flow control boards, valves, High and Low limits.

Flow Control Boards - Each gas has an individual flow control board associated with the gas. The board is located in the flow head unit and communicates to the 9210 controller. The flow control board has a comm port on it that can be switched between RS-485 and RS-232. The board must be in the RS-485 mode to communicate with the 9210. The RS-232 mode allows for communication directly to a PC running the configuration software. The RS-232 mode allows for downloading of flow curves and troubleshooting. On the front of the flow head unit the LED display shows flow of each gas in SCFH. The LED’s on the front of the unit display the following: Auto/Manual, Alarm, V1, V2.

Auto/Manual - When the Auto/Manual LED is ON the board is in the Auto Mode being controlled by the 9210. The switch on the front of the control panel for each gas allows for the board to be put in Auto, Hand (Manual) or OFF. The LED will be OFF when the switch is in Hand position. The operator can turn the valve wheel by hand in this condition.

ALM – This indicator shows when the board is in an Alarm condition. Alams include max range or high limit switch made.

V1 – V1 indicates the direction the valve is moving. The LED is OFF when the valve is closing and ON when the valve is opening.

V2 – V2 indicates the board is given a Run/Stop command. The LED is OFF when the valve is receiving a Stop signal. The LED is ON when the valve is being given a Run signal.

Valves - Each gas has a needle valve attached to a motor. The motor drives the needle valve via a worm gear. The needle valve shaft has a wheel attached with a set screw that allows the valve to be turned by hand. If adjusting the wheel by hand unplug the connector from the drive so the 9210 is not trying to open or close the valve during hand adjustment.

Limit Switches - Each valve has a limit switch that will not allow the valve to open past a preset limit. These upper limits need to be set in the field for each gas. Before setting the upper limit, the maximum SCFH needs to be known for each flow meter. Instructions for setting the upper limits are as follows:

1.Loosen the set screw on the wheel.

2.Send a setpoint to the valve to obtain the maximum flow desired.

3.Allow the valve to settle at the desired flow.

4.Pull the wheel up till the limit switch is activated.

5.Tighten set screw.

6.Repeat for each valve.

7.Drive each valve closed and then open past the max range to test the limit switch. Be sure to have the event for that specific flow meter turned on under manual events.

Mass Flow Meters

The Mass Flow Meters are located below the Flow Head Unit. The flow meters send a 4-20ma signal to the flow boards to indicate actual flow. If there is no flow it will trigger a Lo FL alarm. If the flow meter has reached its maximum, all LED’s will be ON and the last one will be flashing. Each Mass Flow meter is calibrated for a specific range of flow depending on the gas associated with the meter.

Gas Solenoids

SSi Manual SERIES 9210-M4557-Nitriding

Page 52 of 52

Image 52
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller About This Manual Controller DescriptionModel 9210 Terminals Connections Ethernet Connections Flash Card & Flash Card Reader Electrical InstallationOperator Interface Screen Saver Nitriding Control System Mode of Operation Installation Mounting Stand-alone Flow Panel Copper Brass Galvanized Steel AluminumTouch-screen Interface Loops Display Temp DetailMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Alarm Ack ChartData Logging using Flash Card M4557 Model 9210 Nitriding Controller Program Edit Configuration Configuration MenuParameter Value Auxiliary Analog Input Shutdown DisplayDate and Time Slave Communications StatusManual Event Control PID Loop SetupChange setpoint overshoot protection Event Run Program Setup Zone / Load TC SetupPort Setup Instrument SetupStep Opcode Temperature Atmosphere Option Zone AssignmentsFurnace Setup None BP Back Pressure TempInternal Loop Instrument 1 Instrument Internal LoopInternal Instrument 1 Instrument Default Wait LimitsFurnace Name Alarm Setup Relay AssignmentAnalog Input Setup Relay Set PointsAnalog Output Setup Passcode and Alarm IP AddressEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Series 9210 Opcodes Programmer Description OpcodesM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Applications Information Standard Event Assignments Typical Nitriding Instrument DesignationsRecipe Step OpCode Temp OptionsJump Recipe High and Low Pressure Switches Vessel Pressure SwitchesFlow Section Nitriding Gas Supply Sample PortsMass Flow Meters Flow Head UnitGas Solenoids Back Pressure Valve Differential Pressure TransmitterDrip Legs Sample Cell SolenoidM4557 Model 9210 Nitriding Controller System Description Specification Display NA Analog outputs isolated OptionalSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM Revision History Description Date MCO #