software installed. The Micrologix 1200 is used in conjunction with the 9210 for alarm and event handling purposes. The
The UPS will provide up to 15 minutes of power in case of power loss. To properly shutdown the Nitriding panel …SHUTDOWN the ADVANTECH screen (see instructions), then open panel door and turn OFF UPS. The panel is now safe for electrical work.
There are NO implied safety devices included with this control system.
The safety system (atmosphere flow and pressure) is the responsibility of the customer.
Nitriding Control System: Mode of Operation -
A typical 9210 Nitriding Control system allows the user to automatically run the Nitriding cycle without requiring operator intervention. The system will set temperature, % Dissociation/Kn, Back Pressure and Gas Flows as part of it’s recipe. To control the % Dissociation/Kn, the 9210 has the ability to adjust the Gas flows at any step of the process. Typically, the Ammonia flow rate is adjusted to achieve the desired
%Dissociation/Kn. This adjustment uses the Trim Enable and Trim Range variables. These variables can be set by the recipe or manually from the Detail screen. Trim Enable determines whether the Gas flow can be adjusted. Trim Range is a +/- band from setpoint that the Gas Flow setpoint can be adjusted to. For example, Ammonia Flow Setpoint = 50,Ammonia Trim Enable = Yes and Trim Range = 20. With these settings the Ammonia Flow setpoint can be adjusted from 30 up to 70. The amount of adjustment is determined by the % Dissociation/Kn control loop. If the % Dissociation/Kn requires more ammonia the setpoint is increased, if less ammonia is required, the ammonia flow setpoint is decreased.