SSI America 9210 Applications Information Standard Event Assignments, Recipe Step OpCode Temp

Page 48

M4557 - Model 9210 Nitriding Controller

Chapter 6 - APPLICATIONS INFORMATION

Standard Event Assignments

To simplify operation and maintain consistency, SSI has adopted the following event assignments.

Event 0

Nitrogen Addition

Event 1

Ammonia Addition

Event 2

Disassociated Ammonia Addition

Event 3

Hydrogen Addition

Event 4

Spare

Event 5

Spare

Event 6

Spare

Event 7

Sample Cell Enable

Event 8

Spare

Event 9

Spare

Event 10

Spare

Event 11

Spare

Event 12

Spare

Event 13

Spare

Event 14

Spare

Event 15

Spare

Typical Nitriding Instrument Designations

Instrument 7 – Nitrogen

Instrument 8 – Ammonia

Instrument 9 – Disassociated Ammonia

Nitriding Recipes/Programs

Nitriding Recipes can be broken down into three stages, Startup, Nitriding and Shutdown

In the Startup phase of the recipe, the furnace starts to heat up and is purged with Nitrogen. As a general rule to assure safe operation of the furnace, the furnace should be purged with Nitrogen long enough to allow for 5 to 7 volume changes. This ensures that it will be safe to add Ammonia and/or Dissociated Ammonia when required. This purge time is determined by calculating the furnaces volume and dividing by the Nitrogen Flow. The startup phase can also start adding ammonia once the desired purge time and temperature has been achieved.

In the Nitriding process stage of the recipe, the temperature and %Dissociation/Kn setpoints are set and the Soak times are set as well. This phase will also enable the Trim enable feature for ammonia to allow for control of the furnace atmosphere to setpoint.

After the Nitriding process stage, the shutdown routine will run. This typically involves, shutting off the Ammonia and Dissociated Ammonia, turning on Nitrogen and lowering the temperature setpoint to allow the furnace to cool. This stage will also sound an alarm indicating the process is complete.

SAMPLE RECIPES

Recipe 1

Step

OpCode

Temp

ATM

Options

S1

Go-Sub

 

 

50

SSi Manual SERIES 9210-M4557-Nitriding

Page 48 of 48

Image 48
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller About This Manual Controller DescriptionModel 9210 Terminals Connections Ethernet Connections Electrical Installation Flash Card & Flash Card ReaderOperator Interface Screen Saver Nitriding Control System Mode of Operation Installation Mounting Stand-alone Flow Panel Copper Brass Galvanized Steel AluminumTouch-screen Interface Loops Display Temp DetailMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Chart Alarm AckData Logging using Flash Card M4557 Model 9210 Nitriding Controller Configuration Configuration Menu Program EditParameter Value Auxiliary Analog Input Shutdown DisplayDate and Time Slave Communications StatusPID Loop Setup Manual Event ControlChange setpoint overshoot protection Event Run Program Setup Zone / Load TC SetupPort Setup Instrument SetupStep Opcode Temperature Atmosphere Option Zone AssignmentsFurnace Setup None BP Back Pressure TempInternal Loop Instrument 1 Instrument Internal LoopDefault Wait Limits Internal Instrument 1 InstrumentFurnace Name Alarm Setup Relay AssignmentAnalog Input Setup Relay Set PointsAnalog Output Setup Passcode and Alarm IP AddressEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Series 9210 Opcodes Programmer Description OpcodesM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Applications Information Standard Event Assignments Typical Nitriding Instrument DesignationsRecipe Step OpCode Temp OptionsJump Recipe High and Low Pressure Switches Vessel Pressure SwitchesFlow Section Nitriding Gas Supply Sample PortsFlow Head Unit Mass Flow MetersGas Solenoids Back Pressure Valve Differential Pressure TransmitterDrip Legs Sample Cell SolenoidM4557 Model 9210 Nitriding Controller System Description Specification Display NA Analog outputs isolated OptionalSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM Revision History Description Date MCO #