SSI America 9210 user manual Internal Instrument 1 Instrument, Default Wait Limits, Furnace Name

Page 27

M4557 - Model 9210 Nitriding Controller

Internal Loop 2

Internal Loop 3

Instrument 1 – Instrument 25

The “Event Inst” selection will allow the user to set the events instrument:

Internal

Instrument 1 – Instrument 25

The “Quench Inst” selection will allow the user to set the quench instrument:

Internal Loop 1

Internal Loop 2

Internal Loop 3

Instrument 1 – Instrument 25

The “End of Quench Event” will allow the user to set the end of quench event. It can be event 0 through event 14.

The “Quench Speed Event” will allow the user to set the quench speed event. It can be event 0 through event 14.

The “Quench Run Event” will allow the user to set the quench run event. It can be event 0 through event 14.

The “Nitrider Bias” selection can be used to adjust the % Dissociation/Kn reading to match Pipette or Metallurgical readings. Setting this value to 5.0 will increase the reading from 20 to 25, whereas setting the value to –5.0will decrease the reading from 20 to 15. This can range from –10.0to 10.0

The “SSI Flow Signal” selection will allow the user to set the flow signal. It can be either Analog or Digital/485.

The “End Recipe Events Clear” selection will allow the user to clear out the events at the end of a recipe. It can be either Yes or No.

Default Wait Limits

Parameter

Value

Temperature Wait Limit

15 °

Atmosphere Wait Limit

10

 

 

 

 

The wait limits are used in the recipe programming. A wait limit allows the program to move to the next step once the process variable (or the actual furnace) has gotten to within the default wait limits that are indicated on this screen.

Highlighting your choice to be changed and pressing the Enter key moves you to a numeric keypad that allows you to enter a new value by touching the appropriate keys. The Temperature Wait Limit can range from 0 to 50 degrees. The Atmosphere Wait Limit can range from 0.00 to 0.49. Pressing the Esc key takes you back to the Menu screen.

Furnace Name

Parameter

Value

Furnace Name

Nitrider

PV1 Name

Dissociation

PV2 Name

Temperature

PV3 Name

Back Pressure

 

 

Select the parameter to edit and press the Enter key to display an alphanumeric keyboard. Enter the name that you wish to be displayed.

SSi Manual SERIES 9210-M4557-Nitriding

Page 27 of 27

Image 27
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller Controller Description About This ManualModel 9210 Terminals Connections Ethernet Connections Electrical Installation Flash Card & Flash Card ReaderOperator Interface Screen Saver Nitriding Control System Mode of Operation Copper Brass Galvanized Steel Aluminum Installation Mounting Stand-alone Flow PanelTouch-screen Interface Temp Detail Loops DisplayMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Chart Alarm AckData Logging using Flash Card M4557 Model 9210 Nitriding Controller Configuration Configuration Menu Program EditParameter Value Slave Communications Status Auxiliary Analog InputShutdown Display Date and TimePID Loop Setup Manual Event ControlChange setpoint overshoot protection Zone / Load TC Setup Event Run Program SetupInstrument Setup Port SetupZone Assignments Step Opcode Temperature Atmosphere OptionInternal Loop Furnace SetupNone BP Back Pressure Temp Internal Loop Instrument 1 InstrumentDefault Wait Limits Internal Instrument 1 InstrumentFurnace Name Relay Assignment Alarm SetupRelay Set Points Analog Input SetupAnalog Output Setup IP Address Passcode and AlarmEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Opcodes Series 9210 Opcodes Programmer DescriptionM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Options Applications Information Standard Event AssignmentsTypical Nitriding Instrument Designations Recipe Step OpCode TempJump Recipe Sample Ports High and Low Pressure SwitchesVessel Pressure Switches Flow Section Nitriding Gas SupplyFlow Head Unit Mass Flow MetersGas Solenoids Sample Cell Solenoid Back Pressure ValveDifferential Pressure Transmitter Drip LegsM4557 Model 9210 Nitriding Controller System Description Display NA Analog outputs isolated Optional SpecificationSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM MCO # Revision History Description Date