The Advantech TPC-642S/642-SE touch screen operator interface utilizing a Compact Flash card allows the unit to data log the parameters setup by a qualified SSi technician. Should a customer not take the data offline in a timely manner, the data will be over-written, the oldest data being that which is over-written first. The following is a description on how this data log system works:

1.When the Advantech operator interface detects that there is less than 5% disk space left on the Compact Flash card, an alarm will be displayed on the main interface screen stating "x% disk space remaining (overwrite at 3%)". In the upper right corner, an ALM is indicated, but because it is not a communications alarm or a 9210 device alarm, the background remains green. This alarm will remain active until more than 5% of disk space is available for writing data log files.

2.If the user does not copy the log data from the disk, it will eventually fall to 2% disk space. At this point, the touch screen will select the oldest compressed file and delete it. It then checks to see if 3% remains. It repeats this procedure until 3% disk space remains. At this point the alarm message changes to "Overwriting data log data!". Because this allows the system to seesaw between 2% and 3%, it will continue to display "Overwriting data log data!" until somebody offloads the files.

Technical concerns and details:

1.If there are not enough compressed files to bring the free space up to 3%, the system will hunt down and kill hourly files. This should only happen if compression would not be running for some reason.

2.If all compressed files and hourly files have been removed and there is still not enough disk space (perhaps a problem with the Compact Flash card), the data logger will not write to the disk until the condition is remedied. (Alarms continues to display)

3.The data log data alarm is the lowest priority. The alarm priorities are touch-screen communications, then 9210 controller/programmer, then disk space.

!Warning: Make sure that the 9210 application has been shut down before removing the flash card

SSi Manual SERIES 9210-M4557-Nitriding

Page 19 of 19

Image 19
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller Controller Description About This ManualModel 9210 Terminals Connections Ethernet Connections Flash Card & Flash Card Reader Electrical InstallationOperator Interface Screen Saver Nitriding Control System Mode of Operation Copper Brass Galvanized Steel Aluminum Installation Mounting Stand-alone Flow PanelTouch-screen Interface Temp Detail Loops DisplayMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Alarm Ack ChartData Logging using Flash Card M4557 Model 9210 Nitriding Controller Program Edit Configuration Configuration MenuParameter Value Slave Communications Status Auxiliary Analog InputShutdown Display Date and TimeManual Event Control PID Loop SetupChange setpoint overshoot protection Zone / Load TC Setup Event Run Program SetupInstrument Setup Port SetupZone Assignments Step Opcode Temperature Atmosphere OptionInternal Loop Furnace SetupNone BP Back Pressure Temp Internal Loop Instrument 1 InstrumentInternal Instrument 1 Instrument Default Wait LimitsFurnace Name Relay Assignment Alarm SetupRelay Set Points Analog Input SetupAnalog Output Setup IP Address Passcode and AlarmEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Opcodes Series 9210 Opcodes Programmer DescriptionM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Options Applications Information Standard Event AssignmentsTypical Nitriding Instrument Designations Recipe Step OpCode TempJump Recipe Sample Ports High and Low Pressure SwitchesVessel Pressure Switches Flow Section Nitriding Gas SupplyMass Flow Meters Flow Head UnitGas Solenoids Sample Cell Solenoid Back Pressure ValveDifferential Pressure Transmitter Drip LegsM4557 Model 9210 Nitriding Controller System Description Display NA Analog outputs isolated Optional SpecificationSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM MCO # Revision History Description Date