M4557 - Model 9210 Nitriding Controller

Zone Assignments

WARNING: This screen should not be changed without consulting SSi at 800-666-4330.

The zone assignment feature allows the SERIES 9210 program to change set points on all instruments of a multi-zone furnace. The SERIES 9210 has up to five (5) temperature and atmosphere zone assignments available. The SERIES 9210 programmer looks for appropriate zone assignments whenever a set point is to be sent to the atmosphere or temperature controller. The temperature set point is sent to every instrument number in the temperature zone assignment.

If the ZONE_OFF (Zone Offset) opcode had been used in the program, the set point sent to the specified zone instrument would have the offset added. For example, a 3-zone pit furnace where the bottom zone usually has a higher set point. The middle zone and the top zone usually have a

lower set point. The bottom zone temperature controller is assigned to zone 1, the middle temperature controllers to zone 2, and the top zone controller to zone 3.

If the first three steps of a program are as shown below, then the bottom zone set point is 1725, the middle zones are 1750, and the top zone is 1800.

Step

opcode

Temperature Atmosphere

Option

1

ZONE_OFF

50

1

2

ZONE_OFF

25

3

3

SETPT

1750

 

The first step sets the offset for zone 1 to –25 degrees; therefore, the bottom zone controller would be sent a set point of 1725 when step 3 is executed. Likewise step 2 sets the offset for zone 4 to 50 degrees. The top zone then receives a set point of 1800. The middle zone controller would receive the 1750. The temperature controller displayed on the Status Display is instrument #2. If instrument #2 were the top zone controller then the Status Display would show the 1800-degree set point.

When using the multi-zone offset feature, the atmosphere and temperature controller assigned as instruments 1 and 2 should be in zones that will not be offset.

SSi Manual SERIES 9210-M4557-Nitriding

Page 25 of 25

Image 25
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller Controller Description About This ManualModel 9210 Terminals Connections Ethernet Connections Flash Card & Flash Card Reader Electrical InstallationOperator Interface Screen Saver Nitriding Control System Mode of Operation Copper Brass Galvanized Steel Aluminum Installation Mounting Stand-alone Flow PanelTouch-screen Interface Temp Detail Loops DisplayMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Alarm Ack ChartData Logging using Flash Card M4557 Model 9210 Nitriding Controller Program Edit Configuration Configuration MenuParameter Value Shutdown Display Auxiliary Analog InputDate and Time Slave Communications StatusManual Event Control PID Loop SetupChange setpoint overshoot protection Zone / Load TC Setup Event Run Program SetupInstrument Setup Port SetupZone Assignments Step Opcode Temperature Atmosphere OptionNone BP Back Pressure Temp Furnace SetupInternal Loop Instrument 1 Instrument Internal LoopInternal Instrument 1 Instrument Default Wait LimitsFurnace Name Relay Assignment Alarm SetupRelay Set Points Analog Input SetupAnalog Output Setup IP Address Passcode and AlarmEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Opcodes Series 9210 Opcodes Programmer DescriptionM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Typical Nitriding Instrument Designations Applications Information Standard Event AssignmentsRecipe Step OpCode Temp OptionsJump Recipe Vessel Pressure Switches High and Low Pressure SwitchesFlow Section Nitriding Gas Supply Sample PortsMass Flow Meters Flow Head UnitGas Solenoids Differential Pressure Transmitter Back Pressure ValveDrip Legs Sample Cell SolenoidM4557 Model 9210 Nitriding Controller System Description Display NA Analog outputs isolated Optional SpecificationSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM MCO # Revision History Description Date