SSI America user manual M4557 Model 9210 Nitriding Controller

Page 43

M4557 - Model 9210 Nitriding Controller

ATMOSPHERE, turns ON the atmosphere alarm and turns OFF the temperature alarm

BOTH, turns ON both the temperature and the atmosphere alarms.

The band limit can be changed by the SET_WAIT opcode.

DOW_INQ This opcode checks the real time clock for the day of the week. This is useful for performing operations on a weekly basis on a specific day. The option data is the day of the week, i.e. SUN, MON, TUE, WED, THU, FRI, and SAT.

EVT_IN This opcode waits for an input event to be turned ON or OFF depending on the option value. The option value is the event number followed by either ON or OFF.

If temperature data and or atmosphere data are specified, they are considered setpoints and will be sent to the appropriate controller.

EVT_OUT The Event Output opcode turns an output ON or OFF event based upon the option value. The option value is the event number followed by either ON or OFF.

If temperature data and or atmosphere data are specified, they are considered setpoints and will be sent to the appropriate controller.

G_SOAK This is a guaranteed soak opcode. The temperature process value must be within the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT opcode. If Load TC Enable is set to ON, this opcode will wait for all temperature inputs selected to be within the deviation band before starting the soak timer.

GHSOAK This is a guaranteed High soak opcode. The temperature process value must be within the setpoint and the high deviation band range to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT opcode. If Load TC Enable is set to ON, this opcode will wait for all temperature inputs selected to be within the acceptable band before starting the soak timer.

GHZSOAK This is a Guaranteed Soak High opcode for a zone. The temperature process value must be above the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT opcode.

GLSOAK This is a guaranteed Low soak opcode. The temperature process value must be within the setpoint and the low deviation band range to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT opcode. If Load TC Enable is set to ON, this opcode will wait for all temperature inputs selected to be within the acceptable band before starting the soak timer.

GLZSOAK This is a Guaranteed Soak Low opcode for a zone. The temperature process value must be below the deviation band to allow the soak timer to run. The option value is the soak time in hours and minutes. The band limit can be changed by the SET_WAIT opcode.

GOSUB The go to subroutine (recipe) opcode is used to call a program and then return to the calling program. This is used to execute standard routines that can be used by many programs. GOSUBs can be stacked up to eight levels. The option data is the program number.

GRAMP This opcode changes the temperature setpoint and/or the atmosphere setpoint linearly over time. The option data is the total ramp time in hours and minutes. The temperature data specifies the final setpoint for the temperature setpoint. The atmosphere data specifies the final value for the atmosphere setpoint. This opcode will cause the setpoint change to wait until all temperature

SSi Manual SERIES 9210-M4557-Nitriding

Page 43 of 43

Image 43
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller Controller Description About This ManualModel 9210 Terminals Connections Ethernet Connections Flash Card & Flash Card Reader Electrical InstallationOperator Interface Screen Saver Nitriding Control System Mode of Operation Copper Brass Galvanized Steel Aluminum Installation Mounting Stand-alone Flow PanelTouch-screen Interface Temp Detail Loops DisplayMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Alarm Ack ChartData Logging using Flash Card M4557 Model 9210 Nitriding Controller Program Edit Configuration Configuration MenuParameter Value Slave Communications Status Auxiliary Analog InputShutdown Display Date and TimeManual Event Control PID Loop SetupChange setpoint overshoot protection Zone / Load TC Setup Event Run Program SetupInstrument Setup Port SetupZone Assignments Step Opcode Temperature Atmosphere OptionInternal Loop Furnace SetupNone BP Back Pressure Temp Internal Loop Instrument 1 InstrumentInternal Instrument 1 Instrument Default Wait LimitsFurnace Name Relay Assignment Alarm SetupRelay Set Points Analog Input SetupAnalog Output Setup IP Address Passcode and AlarmEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Opcodes Series 9210 Opcodes Programmer DescriptionM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Options Applications Information Standard Event AssignmentsTypical Nitriding Instrument Designations Recipe Step OpCode TempJump Recipe Sample Ports High and Low Pressure SwitchesVessel Pressure Switches Flow Section Nitriding Gas SupplyMass Flow Meters Flow Head UnitGas Solenoids Sample Cell Solenoid Back Pressure ValveDifferential Pressure Transmitter Drip LegsM4557 Model 9210 Nitriding Controller System Description Display NA Analog outputs isolated Optional SpecificationSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM MCO # Revision History Description Date