SSI America 9210 user manual Zero Output

Page 35

M4557 - Model 9210 Nitriding Controller

The next screen is the Zero Input 3 Range 2 screen. This screen will allow the user to set the zero scale for Input 3 Range 2. A value of 0 millivolts will need to be sourced to the inputs. For a zero calibration, enter a 0 as the value of the terminal to correctly calibrate the inputs. The current Input 3 value will be displayed near the bottom of the screen as “Current Input 3 value: xxxx.xx uV”. The progress bar at the bottom of the screen will display the calibration progress.

The next screen is the Span Input 3 Range 2 screen. This screen will allow the user to set the span value for Input 3 Range 2. A suggested value will be displayed next to the Calibrate button (“sugg. 65.000 mV”). The current Input 3 value will be displayed near the bottom of the screen as “Current Input 3 value: xxxx.xx uV”. The progress bar at the bottom of the screen will display the calibration progress.

The next screen is the Zero Output 1 screen. This screen will allow the user to set the zero value for Output 1. Measured at terminals 24(-) and 25(+) for this step. The progress bar at the bottom of the screen will display the calibration progress.

Zero Output 1

Enter span output current (mA)

Calibrate

Edit

<-- Back

 

Skip

 

Next -->

 

DONE

Span Output 1

Entered measured output current (mA) Calibrate

Edit

<-- Back

 

Skip

 

Next -->

 

DONE

The next screen is the Zero Output 2 screen. This screen will allow the user to set the zero value for Output 2. Measured at terminals 26(-) and 25(+) for this step. The progress bar at the bottom of the screen will display the calibration progress.

The next screen is the Span Output 1 screen. This screen will allow the user to set the span value for Output 1. Measured at terminals 24(-) and 25(+) for this step. The progress bar at the bottom of the screen will display the calibration progress.

Zero Output 2

Enter zero output current (mA)

Calibrate

Edit

<-- Back

 

Skip

 

Next -->

 

DONE

SSi Manual SERIES 9210-M4557-Nitriding

Page 35 of 35

Image 35
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller Controller Description About This ManualModel 9210 Terminals Connections Ethernet Connections Operator Interface Screen Saver Electrical InstallationFlash Card & Flash Card Reader Nitriding Control System Mode of Operation Copper Brass Galvanized Steel Aluminum Installation Mounting Stand-alone Flow PanelTouch-screen Interface Temp Detail Loops DisplayMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Data Logging using Flash Card ChartAlarm Ack M4557 Model 9210 Nitriding Controller Parameter Value Configuration Configuration MenuProgram Edit Slave Communications Status Auxiliary Analog InputShutdown Display Date and TimeChange setpoint overshoot protection PID Loop SetupManual Event Control Zone / Load TC Setup Event Run Program SetupInstrument Setup Port SetupZone Assignments Step Opcode Temperature Atmosphere OptionInternal Loop Furnace SetupNone BP Back Pressure Temp Internal Loop Instrument 1 InstrumentFurnace Name Default Wait LimitsInternal Instrument 1 Instrument Relay Assignment Alarm SetupRelay Set Points Analog Input SetupAnalog Output Setup IP Address Passcode and AlarmEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Opcodes Series 9210 Opcodes Programmer DescriptionM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Options Applications Information Standard Event AssignmentsTypical Nitriding Instrument Designations Recipe Step OpCode TempJump Recipe Sample Ports High and Low Pressure SwitchesVessel Pressure Switches Flow Section Nitriding Gas SupplyGas Solenoids Flow Head UnitMass Flow Meters Sample Cell Solenoid Back Pressure ValveDifferential Pressure Transmitter Drip LegsM4557 Model 9210 Nitriding Controller System Description Display NA Analog outputs isolated Optional SpecificationSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM MCO # Revision History Description Date