M4557 - Model 9210 Nitriding Controller
Alarm Setup
The Alarm Setup menu is a
Parameter | Value |
Setpoint | 2500 |
Alarm Type | PV2 proc high |
Hysteresis | 1 |
|
|
Using the lower blue up and down arrow keys, select the parameter to modify, and then press the Enter button. The “Setpoint” selection will allow the user to enter the setpoint for the alarm. This will display a numeric keypad. This can range from
Process High
Process Low
Band, Normally Open
Band, Normally Closed
Deviation, Normally Open
Deviation, Normally Closed
The bottom level has the following options:
PV 1 Value
PV 2 Value
PV 3 Value
Input 1 Value
Input 2 Value
Input 3 Value
PO1 Value
PO2 Value
PO3 Value
The “Hysteresis” selection will allow the user to set the hysteresis. This will display a numeric keypad. This can range from 0 to 9999.
If you are configuring more than one alarm, follow the above instructions for each alarm that you are configuring.
Relay Assignment
This menu selection allows the user to assign the action to the selected Relay Output.
All eight of the 9210’s relay outputs are assigned in this screen. To select a Relay Output to modify, use the up or down arrow keys to highlight the event.
Highlighting the “Assignment” selection that you wish to assign and pressing the Enter button takes you to a screen that has the following choices
•Loop 1 fwd
•Loop 1 rev
•Loop 2 fwd
•Loop 2 rev
•Loop 3 fwd
•Loop 3 rev