M4557 - Model 9210 Nitriding Controller

Alarm Setup

The Alarm Setup menu is a two-level screen. The first level allows you to select the alarm – Alarm1 Alarm 3. The Second level scrolls through the alarm parameters.

Parameter

Value

Setpoint

2500

Alarm Type

PV2 proc high

Hysteresis

1

 

 

Using the lower blue up and down arrow keys, select the parameter to modify, and then press the Enter button. The “Setpoint” selection will allow the user to enter the setpoint for the alarm. This will display a numeric keypad. This can range from –9999to 9999. The “Alarm Type” selection will allow the user to set the type of alarm. This will display a two-level screen. The top level has the following options:

Process High

Process Low

Band, Normally Open

Band, Normally Closed

Deviation, Normally Open

Deviation, Normally Closed

The bottom level has the following options:

PV 1 Value

PV 2 Value

PV 3 Value

Input 1 Value

Input 2 Value

Input 3 Value

PO1 Value

PO2 Value

PO3 Value

The “Hysteresis” selection will allow the user to set the hysteresis. This will display a numeric keypad. This can range from 0 to 9999.

If you are configuring more than one alarm, follow the above instructions for each alarm that you are configuring.

Relay Assignment

This menu selection allows the user to assign the action to the selected Relay Output.

All eight of the 9210’s relay outputs are assigned in this screen. To select a Relay Output to modify, use the up or down arrow keys to highlight the event.

Highlighting the “Assignment” selection that you wish to assign and pressing the Enter button takes you to a screen that has the following choices

Loop 1 fwd

Loop 1 rev

Loop 2 fwd

Loop 2 rev

Loop 3 fwd

Loop 3 rev

SSi Manual SERIES 9210-M4557-Nitriding

Page 28 of 28

Image 28
Contents SSi’s Nitriding Control System Table of Contents M4557 Model 9210 Nitriding Controller Safety M4557 Model 9210 Nitriding Controller About This Manual Controller DescriptionModel 9210 Terminals Connections Ethernet Connections Flash Card & Flash Card Reader Electrical InstallationOperator Interface Screen Saver Nitriding Control System Mode of Operation Installation Mounting Stand-alone Flow Panel Copper Brass Galvanized Steel AluminumTouch-screen Interface Loops Display Temp DetailMenu Display Menus M4557 Model 9210 Nitriding Controller Program Display Alarm Ack ChartData Logging using Flash Card M4557 Model 9210 Nitriding Controller Program Edit Configuration Configuration MenuParameter Value Auxiliary Analog Input Shutdown DisplayDate and Time Slave Communications StatusManual Event Control PID Loop SetupChange setpoint overshoot protection Event Run Program Setup Zone / Load TC SetupPort Setup Instrument SetupStep Opcode Temperature Atmosphere Option Zone AssignmentsFurnace Setup None BP Back Pressure TempInternal Loop Instrument 1 Instrument Internal LoopInternal Instrument 1 Instrument Default Wait LimitsFurnace Name Alarm Setup Relay AssignmentAnalog Input Setup Relay Set PointsAnalog Output Setup Passcode and Alarm IP AddressEvent Control Valve Setup M4557 Model 9210 Nitriding Controller Zero Output Menu Item Security Level Read/Write Raw Data Analog Input Board Setup AUX SP Configuration Programs Overview M4557 Model 9210 Nitriding Controller Series 9210 Opcodes Programmer Description OpcodesM4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller M4557 Model 9210 Nitriding Controller Applications Information Standard Event Assignments Typical Nitriding Instrument DesignationsRecipe Step OpCode Temp OptionsJump Recipe High and Low Pressure Switches Vessel Pressure SwitchesFlow Section Nitriding Gas Supply Sample PortsMass Flow Meters Flow Head UnitGas Solenoids Back Pressure Valve Differential Pressure TransmitterDrip Legs Sample Cell SolenoidM4557 Model 9210 Nitriding Controller System Description Specification Display NA Analog outputs isolated OptionalSensor General Frequency Technical Information Data=xCRLF Error messages System errors Nitriding Sample Cell cleaning TC Type Range in mV E80 J80 K80 N80 NNM Revision History Description Date MCO #