THERMOSTAT LOCATION (SG MODELS)

CAUTION — Do not run wire behind flanges of Header Plate or in any location where it might be damaged.

Millivolt wall thermostats are specially designed for use on self- generating systems. They should never be used on line or low voltage A.C. circuits.

Interior Wall — The thermostat should be installed on an inside wall away from the furnace but in the same room.

It is important to use wire of a gauge proper for the length of the wire:

RECOMMENDED WIRE GAUGES

Maximum Length

Wire Gauge

1' to 10'

18

10' to 25'

16

25' to 35'

14

Proper operation depends on a good pilot flame. The flame must cover the top of the thermopile. Cleaning of the pilot orifice and burner may be required due to spiders.

System Check (Figure 7)

Amillivolt meter is required to check the system. Millivolt readings should be:

Across the thermopile terminals, 400-450 millivolts with thermostat OFF.

Across the thermopile terminals, 150-250 millivolts with thermostat ON.

Across the thermostat wires at the valve, less than 30 millivolts with thermostat ON.

Across the thermostat wires at the thermostat, less than 5 millivolts with thermostat ON. (Dirty pilot or low pressure will reduce readings.)

Connect thermostat wires to gas valve as shown in Figure 7.

Figure 7

12425-10-1008

Page 11

Image 11
Contents Installation Instructions Table of Contents This is a Heating Appliance Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASIntroduction SpecificationsInsulated Vent Enclosure Recommended Vent ConfigurationOval all parts purchase locally Recommended Gas Pipe Diameter Installing a New Main Gas CockPressure Testing of the Gas Supply System GAS SupplyROUGH-IN Instructions ClearancesVentilation and Combustion AIR Location ALL ModelsPlastering Figure Installing Furnace FigureFinishing Instructions Outer Casing Figure Installing Control DoorSystem Check Figure Recommended Wire GaugesThermostat Location SG Models What to do if YOU Smell GAS Lighting InstructionsProper Pilot Flame Vent Safety Shutoff SystemProper Main Burner Flame If Pilot Does Not Light By Any Means TroubleshootingMain Gas Valve Does Not Open When Thermostat Is Turned On Pilot Does Not LightIndex Description Parts ListHOW to Order Repair Parts Parts View Instructions Remote Bulb Control Installation InstructionsModels GWT-25 RB, GWT-35 RB, GWT-50 RBGWT-25 SG, RB, GWT-35 SG, RB, GWT-50 SG, RB Optional Blower Installation InstructionsGWTB-2 for Models Fan Control WiringParts List Service Notes Instructions Pour L’INSTALLATION Manuel DU Propriétaire Section Table DES MatièresCeci EST UN Appareil DE Chauffage Information Importante DE SécuritéInformation DE Sécurité Pour LES Utilisateurs DE Propane Avertissement IntroductionSpécifications Enceinte Isolée de l’Évent Configuration Recommandée Pour L’ÉVACUATIONOvale de 4 102mm toutes les pièces sont achetées localement Vérifier les Pressions de Gaz Le Diamètre recommandé de tuyau de gazAlimentation EN GAZ Test de Pression du Système dAlimentation de GazInstructions Sommaires EMPLACEMENT- Pour Tous LES ModèlesEspaces Libres AIR DE Ventilation ET DE CombustionPlâtrage Figure Installer la Fournaise FigureInstructions Pour LA Finition Paroi Extérieure Figure Installer LA Porte DE CommandeVérification du Système Figure Emplacement DU Thermostat Modèles SGOuvert Instructions DallumageQuoi Faire SI Vous Sentez LE GAZ Veilleuse FerméLE Système DE Fermeture DE Sûreté DE L’ÉVENT Aspect Convenable DE LA Flamme DE LA VeilleusePanne de la Veilleuse lors d’un Fonctionnement Normal Détection DES DéfectuositésVeilleuse ne s’Allume pas En Aucune Façon, la Veilleuse ne s’Allume PasListe DES Pièces Façon DE Commander LES Pièces DE RéparationVUE DES Pièces Modèles Instructions Pour L’INSTALLATION DE LA CommandeGWT-25-RB, GWT-35-RB, GWT-50-RB Sur un Mur en Placoplâtre Sur un Mur SolideHuiler Commande du VentilateurListe des Pièces AvertissementPage Instrucciones DE Instalacion Manual DEL Propietario Sección Tabla DE ContenidoEste ES UN Aparato DE Calefacción Importante Información DE SeguridadInformación DE Seguridad Para Usuarios DE GAS Propano LP Especificaciones IntroducciónCercamienos Aislados para Humeros Configuración Recomendada Para VentilaciónProbando la Presión en el Sistema de Gas Abastecimiento DE GASDiámetro Recomendado de Tubería Instalando una Nueva Llave para VálvulaInstrucciones DE Bosquejo Espacios LibresVentilación Y Aire Para Combustión Ubicación Todo ModeloInstalando el Calentador Figura Instrucciones DE AcabadoEnyesando Figura Instalando LA Puerta DE Control Carcasa Exterior FiguraInspección del Sistema Figura Instalación DEL Termostato Modelos SGGalgas Recomendadas DEL Alambre Forzar o reparar puede causar un incendio o explosión Instrucciones DE EncendidoQUÉ Hacer SI Huele GAS Flama Correcta DEL Piloto Flama Correcta DEL Quemador PrincipalApago del Piloto Durante Operación Normal Si el Piloto no Enciende de Ninguna ManeraÍndice Parte Descripción Lista DE PartesComo Pedir Partes DE Repuesto Vista DE Partes Instrucciones ModelosIndice Parte Descripción Instalación del Ventilador con Conexión Eléctrica Directa Instalación del Ventilador Usando un Enchufe de Tres PuntasSobre una Pared Sólida Sobre una Pared de YesoLista DE Partes AdvertenciaNotas DE Servicio Técnico