RECOMMENDED VENT CONFIGURATION
Note: No vent equipment supplied with furnace.
4" Oval (all parts purchase locally)
1.Type
2.Single story type
3.
plate spacers at the first floor ceiling and one pair of fire stop spacers at each successive ceiling level.
Type
Insulated Vent Enclosure
Gravity vented wall furnaces installed in buildings with flat roofs can have poor venting. The cold vent pipe will have a delay in proper venting and cause the wall furnace to shut "off" by the vent safety switch. To prevent delayed venting as well as condensation of flue products an insulated vent enclosure is recommended.
Use Type B vent pipe and maintain at least a one inch (25mm) clearance to combustibles.
Use metal thimble to protect vent pipe as it passes through combustibles.
Baseplate Gasket is factory installed on header. Baseplate attaches to header with screws.
Stud space around gas vents must be free of obstructions and building paper.
Uninsulated
Attention: The main burner uses room air for combustion. As the gas/air mixture is injected into the main burner, there is also the flow of dust and lint particles into the main burner.
Dust and lint accumulation inside the main burner will result in a yellow main burner flame and possible sooting inside the combustion chamber and vent pipe. To clean main burner refer to Page 13, "Proper Main Burner Flame."