184
PRO SWITCHING SYSTEM
Variable: 1.3.6.1.4.1.509.1.7.1.5.[sigAlarmIndex]
where [sigAlarmIndex] is a number (from 1 to
32) of an alarm definition to which the signal
state (mark, space, etc.) is assigned.
Example: Set MARK as the signal state alarm condition of
alarm index 1.
Operation: Set
Variable: 1.3.6.1.4.1.509.1.7.1.5.1
Set Value: mark(1)
sigAlarmSeconds
Description: The number of seconds required to establish
an alarm condition. If the alarm criteria remain
in the alarm state for the specified length of
time, an alarm condition has been established.
You can SET and GET the value of this
variable.
Parameters: 1 to 30,000 seconds
MIB Path: 1.3.6.1.4.1.509.1.7.1.6
iso(1).org(3).dod(6).internet(1).private(4).ent
erprises(1).Hadax(509).
IntelliSwitch2000(1).sigAlarmTable(7).sigAlar
mEntry(1).
sigAlarmSeconds(6)
Variable: 1.3.6.1.4.1.509.1.7.1.6.[sigAlarmIndex]
where [sigAlarmIndex] is a number (from 1 to
32) of an alarm definition to which the alarm
seconds entry (from 1 to 999 seconds) is
assigned.
Example: Set 5 seconds as the length of time required to
set off an alarm for alarm index 1.
Operation: Set
Variable: 1.3.6.1.4.1.509.1.7.1.6.1
Set Value: 5