Alarm Name

Default

Definition

Priority

 

 

 

 

 

Comb Temp Hi Limit Exceeded

User

The combined temperature of an entire Standard Cir-

 

 

cuit or Case Control Circuit has risen above its pro-

 

 

grammed high temperature setpoint.

Comb Temp Low Limit Exceeded

User

The combined temperature of an entire Standard Cir-

 

 

cuit or Case Control Circuit has fallen below its pro-

 

 

grammed low temperature setpoint.

Commission failed-chk network

50

Commission of Echelon controller failed; binding of

 

 

NV was not successful. Check the Echelon network.

Communication Port 1 Is Down

20

E2 cannot communicate with the RS232 port on the

 

 

E2 main board. The E2 main board likely needs

 

 

repair or replacement.

Communication Port 2 Is Down

20

E2 cannot communicate with the RS485 network port

 

 

on the E2 main board. The E2 main board likely

 

 

needs repair or replacement.

Communication Port 3 Is Down

20

E2 cannot communicate with the modem slot on the

 

 

E2. The E2 main board likely needs repair or replace-

 

 

ment.

Communication Port 4 Is Down

20

COM4 is used by service personnel to attach hard-

 

 

ware used in test or debug functions. This alarm indi-

 

 

cates the port that allows E2 to communicate with

 

 

these devices is faulty. The E2 board likely needs

 

 

repair or replacement.

Communication Port 6 is down

20

E2 cannot communicate with port 6 on the E2 main

 

 

board.

Completed Firmware Update

50

The E2’s firmware was successfully updated.

Config Loss - Chg In Tmpl Rev.

15

Due to a difference between configuration templates

 

 

in a previous E2 version and templates in the current

 

 

version, configuration data could not be restored.

Config Loss-CRC Error

15

Due to an internal error, E2 has lost configuration

 

 

data.

Config Loss-File CRC Error

15

Due to an internal error, E2 has lost configuration

 

 

data.

Config Not Saved To Flash

20

E2 could not save configuration data to flash mem-

 

 

ory.

Controller (or Device) Absent From

20

The current E2 could not find the specified E2, I/O

Network

 

board, or Echelon controller

Controller Reset

50

An ARTC/MultiFlex RTU has gone through a reset.

Controller Shutdown

50

The E2 has gone through a shutdown.

Controller Startup

50

The E2 has re-started after a shutdown.