6.3.7Copeland Discus with Core- Sense Protection

Figure 6-7- Copeland Discus Compressor

The Discus application can monitor semi-hermetic

compressors using the MODBUS network on E2 versions

3.01and above. The E2 monitors and records semi-her- metic compressor information. The Discus application has extensive logging capabilities that record a compressor’s Run History, Fault History, and Alarm Status.

The Copeland Discus is supported on E2 RX-300, CX- 400 and above.

6.3.8Light Commercial Thermo-

stat

The Light Commercial Thermostat communicates with the E2 using the MODBUS network. The thermostat will enable the E2 to read status information from the device as well as send operational setpoints to the device. The ther- mostat is available on E2 versions 3.02 and above.

6.3.8.1Thermostat Inputs

The E2 application will provide support for external real time inputs to the thermostat. These inputs are:

•Zone Temperature •Minimum Damper Position •Outside Air Temperature •Inside Humidity

If these inputs are connected to valid values, they are sent to the thermostat to be used in place of any locally connected sensors of the same type. If local sensors are present and meant to be used, the associated inputs on the E2 application should be left disconnected.

6.3.8.2Advisory and Alarms

The Light Commercial Thermostat also supports diag- nostic functions. When a diagnostic code is sent to the E2 from the thermostat, the E2 application will identify the code and generate the corresponding advisories in the advisory log.

Diagnostic Alarms

Each of these configurable diagnostic alarms in the E2 can be set to Disabled, Failure, Alarm, or Notice with an accompanying priority setting.

The diagnostic alarms supported are:

Diagnostic Alarm

Descriptions

E2 Advisory

 

 

 

Heating Two Hours

Thermostat did not see a rise in supply temperature when heating was

Heating Problem Detected

 

called for.

 

 

 

 

Heat Continuous

In heat or backup heat mode, thermostat opens latching relay contacts if

Heat Shutdown – Temp too high

 

temperature is over 10°F above setpoint.

 

 

 

 

Temperature Sensor Fail

If heating or cooling is engaged, and either the indoor temperature sensor

Incorrect Sensor Wiring

 

reading or the supply air temperature sensor reading starts moving the

 

 

opposite way faster than it was before the heating or cooling was engaged,

 

 

the thermostat reports a diagnostic message, and shuts down the operation.

 

 

 

 

Stuck Key

A stuck key (closed) has been detected on the thermostat.

Stuck Key Detected

 

 

 

Unexpected Temperature

Thermostat has detected a failure of the internal space temperature sensor,

Failed Sensor or Bad Wiring

Rise

or the O/B wiring is incorrect.

 

 

 

 

Table 6-5-Diagnostic Alarm Outputs

6-8 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011