XEV22D DRIVER TO E2 INSTALLATION GUIDE

13 14 15 16 17 18 19 20 21

XEV22D

HOT KEY

1

2

4

5

6

7

8

11

12

1.Connect the MODBUS Network to the RS-485 Connector on the E2 PIB board (Belden 8641 recommended).

2.Note to wire the RS-485 +/- polarity at the E2 in the reverse of the XEV22D device.

3.Position the three termination jumpers to the UP (terminated) position to provide RS-485 termination at the E2.

4.Do not connect the shield of the MODBUS network to the E2 PIB center terminal. Instead, use a 100 ohm ½ watt resistor to connect the MODBUS cable shield to earth ground.

5.At the XEV22 device, wire the MODBUS cable to the RS-485 +/- terminals and connect the MODBUS shield to the pin 16 terminal.

6.Terminate the end of the MODBUS network at the last device on the daisy chain with the MODBUS termination block

(P/N 535-2711), or by connecting a 150 ohm resistor between the MODBUS +/- terminals.

For more information, please refer to the XVE22D user manual P/N 026-1206.

637-4890 COM4 ON E2 PIB

RS-485 -2A RS-485

+ 0V

+ 0V

637-4890 COM4 ON E2 PIB

RS-485 -2A

+ 0V

TO DEVICE

RS-485

+0V

RESISTOR

100OHM ½ WATT

EARTH GROUND

CONNECTION

MODBUS SHIELD TO PIN 16

TERMINAL OF DEVICE

13 14 15 16 17

 

 

XEV22D

1

2

4

5

 

_

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

WIRE BLACK TO +

WIRE WHITE TO_

REVERSE POLARITY OF +/- ON RS-485 CABLE FROM E2 TO DEVICE

13 14 15 16 17

LAST XEV22D

DEVICE

1 2 4 5

+

_

 

WIRE BLACK TO +

WIRE WHITE TO

MODBUS TERMINATION

FROM E2 PIB BOARD OR OTHER RS-485 MODBUS DEVICE

BLOCK (P/N 535-2711) 150 OHM

TERMINATE LAST DEVICE ONLY