(2 × 4VA ) + (1 × 40VA ) = 48VA

2.Use a transformer that has a power rating equal to or higher than the total calculated VA (see Table 8-3).

Example: Boards totaling 48VA can be connected to either a 50VA or 75VA transformer.

Unit

amps

VA

VAC

Center

 

 

 

 

tapped?

E2

1.66

40

24

No

ESR8

2.4

75

24

No

 

 

 

 

 

TD3

0.11

4

24

No

 

 

 

 

 

CC-100/

Power supplied by Power Module

CS-100

 

 

 

 

Table 8-4- Device Power Requirements

Refer to the installation guides on the next few pages for instructions on how to install these boards on the Eche- lon Network.

8.7LEDs

The Echelon Board LEDs can be used to determine the status of normal operating parameters for the board.

 

Echelon Board

Status

 

 

 

 

 

Red (D1) (Reset)

ON: The Echelon port is being

 

 

held in reset or if momentary it

 

 

means the board has gone

 

 

through reset

 

Red (Service)

During normal operation this

 

 

LED should be off. If the Ser-

 

 

vice Pin is pressed, this LED

 

 

will come on.

 

 

If the LED is blinking, the node

 

 

does not have its Subnet/

 

 

Node address set. (E2 should

 

 

set this during the first power -

 

 

up sequence where the user

 

 

will be asked in which Subnet

 

 

to put the controller (E2 will al-

 

 

ways be Node = 1 on the net-

 

 

work).

 

 

If the LED is blinking, then try

 

 

resetting the E2. If this does

 

 

not correct the problem, re-

 

 

place the Echelon board.

ON (no blinking): Replace the Echelon board. The Neuron processor has lost its applica- tion program.

Table 8-5- Echelon LED Status

8.8Open Echelon Device Connectivity

Open-Echelon E2s must be ordered pre-configured from Retail Solutions. Open-Echelon licenses must be purchased and enabled on units, and are not transferrable to other units without assistance from Retail Solutions. Call 770-425-2724for technical assistance or your sales representative. Your sales representative will know which devices your unit will connect to.

8.8.1Configuring Echelon Devices

Login to the controller and enter the desired number of Echelon devices to be added in the Connected I/O screen. From the Main Menu:

1.Select (System Configuration)

2.Select (Network Setup)

8-4 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Page 90
Image 90