Appendix D: PID Control

Introduction to PID Control

 

output after each update are made by three different modes

 

 

 

 

of control: Proportional (“P”) Mode, Integral (“I”) Mode,

PID Control is a specialized method of closed-loop

 

and Derivative (“D”) Mode. Each mode of control makes

control that strives to maintain equality between an input

 

its own adjustment to the output percentage, and the three

value and a user-defined setpoint by operating a device or

adjustments are added to the previous output percentage to

a number of devices at somewhere between 0% and 100%

determine the new output percentage. In mathematical

of full capacity.

 

 

 

terms, every update will affect the output percentage as

PID Control works by making adjustments to the out-

follows:

 

 

put at a constant rate called the update rate (usually 2-6

 

NEW OUT% = OLD OUT% + (“P” mode adjustment) + (“I” mode

seconds). For every update that occurs, PID Control takes

a reading from the input sensor or transducer, measures the

adjustment) + (“D” mode adjustment)

 

 

distance between the input and the setpoint (also called the

Each of the three modes (P, I, and D) serves a different

error), makes a series of calculations, and adjusts the out-

put percentage in such a way as to move the input towards

and important purpose, as described below:

the setpoint in the most efficient manner.

 

 

 

The “calculations” that determine the new value of the

 

 

 

 

 

 

 

P

 

 

Tries to stop the error from changing. Measures difference

 

Proportional Mode

 

between current and previous error, and adjusts output per-

 

 

centage to prevent any further movement.

 

I

 

 

Tries to bring the error to zero (input = setpoint).

 

Integral Mode

 

 

 

 

D

 

 

Tries to slow or stop a rapidly changing error so P and I

 

Derivative Mode

 

Modes may effectively work to eliminate it.

 

 

 

 

 

Proportional (“P”) Mode

The Proportional Mode in PID determines the system’s immediate reaction to a change in the error. Proportional Mode simply analyzes the difference between the current error and the previous error. Based on the size of this dif- ference, Proportional Mode will make a change to the out- put in an attempt to stabilize the input value and keep it from changing any further.

Mathematically, the following equation determines the “P” Mode adjustment for a single update:

“P” mode adjustment = Kp (E – E-1)/TR

Kp = proportional constant

E = current error

E-1= error during last update

TR = throttling range

of input value units between a 0% output and a 100% out- put. For example, in a Case Control application, the Throt- tling Range would be the number of degrees between the input temperature that would result in a 0% output and the temperature that would cause a 100% output. Therefore, the Throttling Range essentially determines the percentage of the output adjustment that will be added to the previous percentage when a change in input occurs.

PID Control places this Throttling Range around the setpoint. As a result, Proportional Mode works to keep the temperature near the setpoint and within the throttling range. In most cases, the Throttling Range straddles the setpoint evenly on both sides, as shown in Figure D-1.However, in some applications such as Condenser Con- trol, the Throttling Range may be placed elsewhere see

Throttling Range

In simplest terms, the Throttling Range is the number

Introduction to PID Control

Appendix D: PID Control D-1

Page 237
Image 237
Emerson E2 operation manual Appendix D PID Control, Proportional P Mode, Throttling Range