Emerson E2 operation manual Outside Temperature Sen Sor, Insertion Temperature Probe

Models: E2

1 273
Download 273 pages 39.74 Kb
Page 46
Image 46

should not be mounted above other sensors that generate heat during operation (such as relative humidity sensors).

The indoor temperature sensor should be between four and six feet from the floor.

3.5.2.2Mounting

Mount the sensor using the screws provided as shown in Figure 3-21.

Figure 3-21- Inside Temperature Sensor Mounting

3.5.3Outside Temperature Sen-

sor

3.5.3.1Location

The outside or ambient temperature sensor should be located on the north side of the building, preferably under an eave to prevent sun-heated air from affecting the tem- perature of the sensor.

3.5.3.2Mounting

The temperature sensor may be mounted using any standard tubing clamp. Retail Solutions also offers an alu- minum cover and clamp (P/N 303-1111)which may be mounted as shown in Figure 3-22(fasteners are not pro- vided).

Figure 3-22- Outside Temperature Sensor with Cover and Clamp

3.5.4 Insertion Temperature Probe

3.5.4.1Location

The 12-inch insertion temperature probe may be used to monitor temperature in either the supply or return air ducts of the AHU or RTU.

3.5.4.2Mounting

The insertion probe may be mounted in any orientation within the duct as long as the probe is in the air flow of the duct. The probe housing should be secured using self-tap- ping screws. A 0.250” diameter hole is required for the probe. Figure 3-23shows the installation of the insertion probe (self-tapping screws are not provided).

Figure 3-23- 12-Inch Insertion Probe Mounting

3.5.5Supply and Return Air Sen-

sors

In addition to the 12-inch insertion temperature probe, Retail Solutions uses the same temperature sensor used for

3-8 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011