Emerson operation manual Networking Overview, 1 E2 I/O Network

Models: E2

1 273
Download 273 pages 39.74 Kb
Page 20
Image 20

Capabilities

CX-

CX-

CX-

100

300

400

 

 

 

 

 

E2 Alarm Panel

7

7

7

 

 

 

 

Energy Meter

30

30

30

 

 

 

 

Enhanced Suction

0

0

4

Group

 

 

 

 

 

 

 

ESR8 ESR Control

0

99

99

 

 

 

 

Flexible Combiner

64

128

128

 

 

 

 

Heat/Cool Control

4

6

8

 

 

 

 

Holiday Schedule

8

16

32

 

 

 

 

HVAC Zone

4

6

12

 

 

 

 

Infrared Leak Detec-

1

16

16

tion

 

 

 

 

 

 

 

Irrigation

2

2

2

 

 

 

 

Lighting Control

6

24

48

 

 

 

 

Logging Group

8

32

32

 

 

 

 

Loop/Sequence Control

8

16

28

 

 

 

 

K5 Ref Scroll

0

0

31

 

 

 

 

MultiFlex ESR

0

31

31

 

 

 

 

MRLDS

24

24

24

 

 

 

 

Performance Alert

0

0

63

 

 

 

 

Power Monitoring

2

8

16

 

 

 

 

Pulse Accumulator

4

8

16

 

 

 

 

RCB Controller

0

32

32

 

 

 

 

RMS Asset

99

99

99

 

 

 

 

Standard Circuit

6

12

32

 

 

 

 

Suction Group

0

0

4

 

 

 

 

TD Condenser Fan

8

16

28

Control

 

 

 

 

 

 

 

TD3 Controller

0

99

99

 

 

 

 

Table 1-3- CX-100, CX-300, and CX-400 Comparison

Capabilities

CX-

CX-

CX-

100

300

400

 

 

 

 

 

Time Schedule

8

16

32

 

 

 

 

Table 1-3- CX-100, CX-300, and CX-400 Comparison

1.4Networking Overview

1.4.1E2 I/O Network

Most of the general purpose input and output commu- nications devices required by the E2 to control refrigera- tion systems are connected to the E2 via the I/O Network. The I/O Network is a simple RS485 three-wire connection that allows data interchange between input boards (which read sensor values and digital closures), output boards (which carry out commands from E2’s control applica- tions), and the E2 itself.

The I/O Network is the same thing as the COM A and COM D Networks found on Retail Solutions’ previous generation of controllers, REFLECS. This allows current owners of Retail Solutions’ Refrigeration Monitor and Control (RMC) or Refrigeration Monitor and Case Control (RMCC) controllers to easily retrofit with an E2 RX with- out need for re-wiring.

1-4 E2 RX/BX/CX I&O Manual