P/N

Sensor

Input Type

 

 

 

 

 

 

 

 

 

 

Wiring

Dip Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

203-5751

Wall-mounted

Down

3.

Use Belden #8771 shielded three-conductor cable or equivalent.

 

relative

 

4.

Connect the RED, BLACK, and WHITE wires to the screw terminals the sensor’s

 

humidity (RH)

 

 

connector as shown in Figure 2. Clip the SHIELD wire.

 

 

5.

Connect the SHIELD and BLACK wires to the 0V terminal of the input board. Con-

 

sensor

 

 

 

 

nect the WHITE wire to the SIG terminal of the input board.

 

 

 

6.

Connect the RED wire to the +12V power terminal on the input board.

 

 

 

7.

Locate the input dip switch for the sensor point, and set to the OFF position (LEFT for

 

 

 

 

MultiFlex, DOWN for 16AI). Refer to the input board’s user manual for locations of

 

 

 

 

the input dip switches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

206-0002

Light Level

Down

 

 

 

 

 

 

 

 

 

 

1.

Wire GREEN ground wire

 

 

 

to odd numbered terminal.

 

 

2.

Wire YELLOW and RED

 

 

 

signal wires to even num-

 

 

 

bered terminal.

 

 

3.

Wire the POWER wire to a

 

 

 

+12VDC source on input

 

 

 

board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

207-0100

Analog Liquid

Down

 

 

 

 

 

 

 

 

 

Level

1.

Connect RED

 

 

 

 

 

power wire to

 

 

 

 

 

+12VDC source

 

 

 

 

 

on input board.

 

 

 

 

2.

Connect BLACK

 

 

 

 

 

 

 

 

 

 

 

 

ground wire to

 

 

 

 

 

odd numbered ter-

 

 

 

 

 

minal.

 

 

 

 

3.

Connect GREEN

 

 

 

 

 

signal wire to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

even numbered

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal.

Table 9-1- Sensor Wiring

9-4 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Page 98
Image 98
Emerson E2 operation manual Wall-mounted Down