Alarm Name

Default

Definition

Priority

 

 

 

 

 

IRLDS: Absorption Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: ADC Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Detector Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Drift Fault

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: General Fault

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Line/Filter Flow Fault

20

A zone on an IRLDS unit has a dirty filter or a

 

 

crimped tube.

IRLDS: Pressure Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Self-Test Failure

20

An IRLDS has failed its self-test procedure.

IRLDS: Temperature Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

IRLDS: Unknown Error

20

The IRLDS has experienced an error not recognized

 

 

by the E2.

IRLDS: Voltage Data Error

20

An internal error has occurred in the IRLDS. Check

 

 

the IRLDS display for error code information, and

 

 

call Retail Solutions service.

ISD Missing Phase Lockout

20

After 10 consecutive missing phase trips, the com-

 

 

pressor is locked out on missing phase lockout.

ISD Missing Phase Trip

99

If any of the 3 phases of power is missing after the

 

 

compressor is called to be on, this advisory is gener-

 

 

ated.

ISD Oil Pressure Lockout

20

If we have been in Low Oil warning for 2 minutes we

 

 

will lock out the compressor.

ISD Welded Contactor

20

If there is voltage on the 3 phase sense inputs 0.5 sec-

 

 

onds after the compressor is called to be off, this

 

 

advisory is generated.

ISD Compressor Module Failure

20

A hardware failure has occurred in the ISD module.

C-8 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Page 230
Image 230
Emerson E2 operation manual Alarm Name Default Definition Priority