P/N

Sensor

Input Type

Wiring

Dip Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

207-1000

Refrigerant

Down

 

 

 

 

 

 

 

Level Trans-

 

1. Wire BLACK ground

 

 

 

 

 

 

ducer (Hansen

 

 

 

 

 

 

 

 

wire from “GND”

 

 

 

 

 

 

Probe)

 

sensor terminal to odd

 

 

 

 

 

 

 

 

numbered board ter-

 

 

 

 

 

 

 

 

minal.

 

 

 

 

 

 

 

 

 

2. Wire GREEN signal wire from “SIGNAL” sensor terminal to even numbered board terminal.

3. Wire RED power wire from “POWER” sen- sor terminal to +12VDC terminal on board.

203-1902

Dewpoint Probe

Up

1.Connect the WHITE and GREEN wires to AC1 and AC2 power terminals.

2. Connect BLACK ground wire to odd numbered board termi- nal.

3. Connect RED signal wire to even numbered board terminal.

Table 9-1- Sensor Wiring

The 16AI, 8IO, and MultiFlex Inputs

Input and Output Setup 9-5

Page 99
Image 99
Emerson E2 operation manual Refrigerant