FAN

AMBIENT

TEMP

WATER

 

SPRAY

 

DISCHARGE

 

OUTLET

PRESSURE

 

 

COIL

DAMPERS

INLET

WATER SUMP

 

TEMPERATURE

 

 

W

MP

 

ATER SU

 

PUMP 1 PUMP 2

 

 

EVAPORATIVE

 

CONDENSER

26509038

 

Figure 11-3- Evaporative Condenser Diagram

Input

Sensor Type

Wiring

Instructions

 

 

 

 

 

Discharge Pressure

500 lb. Eclipse

see Table 9-1 on

 

transducer

page 9-3

 

 

 

Ambient Temp

Temperature

see Table 9-1 on

 

 

page 9-3

 

 

 

Water Sump Temp

Temperature

see Table 9-1 on

(Evap. only)

(Immersion)

page 9-3

 

 

 

Override Temp Sen-

Temperature

see Table 9-1 on

sors (Evap. only)

(Pipe-Mount)

page 9-3

 

 

 

Table 11-3- Suction Group Inputs

 

Wire Output

Set Fail-safe Dip

 

Output Device

Board Contacts

Notes

 

to:

Switch to:

 

 

 

 

 

 

 

 

Condenser Fan

N.C.

N.C. (up)

To ensure condensing during network and power failure, con-

(Single-Speed)

 

 

denser fans should all be configured normally closed (N.C.)

 

 

 

 

Condenser Fan

N.C.

N.C. (up)

The fan should operate at 100% during loss of communication

Relay (Variable-

 

 

with E2.

Speed)

 

 

 

 

 

 

 

Dampers (Evap.

N.C.

N.C. (up)

Dampers should be open during communication loss (N.C.).

only)

 

 

 

 

 

 

 

Evaporator Pumps

N.C. (see note)

N.C. (see note)

Some condensers have dual pumps that cycle at even intervals.

(Evap. only)

 

 

One pump should be wired N.C. and the other N.O., so that only

 

 

 

one pump runs during communication loss.

 

 

 

 

Variable-Speed Fan

None (analog point)

None (analog point)

This 4AO or 8IO analog point sends the 0-100% fan speed sig-

Output (to inverter)

 

 

nal to the inverter.

 

 

 

 

Table 11-4- Suction Group Outputs

11.3 Standard Circuits

Refrigerated cases that do not use case controllers are controlled by Standard Circuit applications. In a Standard Circuit application, the E2 is responsible for all case mon- itoring and control; it uses the RS485 I/O Network to both gather case temperature inputs and activate or deactivate the liquid line solenoids, defrost modes, and fans. Also, circuits that use ESR8s and MultiFlex ESRs are controlled using Standard Circuits.

NOTE: Do not set up a Standard Circuit appli- cation for a case that uses a CC-100 or CCB case controller. These cases must use Case Cir-

cuit Control applications (see Section 11.4, Case Con- trol Circuits).

11.3.1 Refrigeration Control

A Standard Circuit application may apply one of four different control methods to a case circuit: the Tempera- ture Monitor method, the Temperature Control method,

Standard Circuits

Software Overview 11-5

Page 147
Image 147
Emerson E2 operation manual Standard Circuits, Refrigeration Control