10.13.2 Checking Online Status

2.

Press (System Configuration)

 

3.

Press (Network Setup)

 

 

4.

Press (Connected I/O Boards & Controllers)

 

 

 

Figure 10-24- Network Summary Screen

You can check all boards that are on either the Echelon Network (E2 controllers) or the I/O Network from the Net- work Status screen (See Figure 10-24). The Network Summary screen displays information such as the Subnet and Node addresses for each board, and the status of Eche- lon and I/O boards.

To get to the Network Summary Screen:

1.Press to open the Main Menu

2.Press (System Configuration)

3.Press (Network Setup)

4.Press (Network Summary)

From the Network Summary screen you can see the total (E2) devices online or offline, status, setup screens, change board or controller names, configure and commis- sion devices, delete a device, and view detailed status screens of controllers.

After determining if a board is offline, turn to Appen- dix E: Troubleshooting.

10.14Set Up Echelon Net-

work

10.14.1Specifying Number of

Devices

To specify the number of devices on the Echelon Net- work, navigate to the Connected I/O screen:

1.Press to open the Main Menu

Figure 10-25- Connected I/O Setup Screen (E2 firmware versions 2.81 and above)

After logging in for the first time, the Connected I/O screen will ask you to specify how many of each type of device will be connected to the E2 you are currently pro- gramming. (Options will vary depending on the type of controller used.)

Unit Number (Echelon Subnet) Each E2 on the Echelon Network must have a different unit number. This can be any number from 1 to 255, but each E2’s number must be unique. No two E2s on the network may have the same unit number.

Enter this number in the Unit Number field. It is rec- ommended you number the first E2 “1” and number the other E2s on the network sequentially (2, 3, 4, etc.).

Unit Name Type a name for the E2 in the Unit Name field.

Unit Controllers (Echelon)

Liquid Ctrls (CC100P/CC100LS) Enter the com- bined number of pulse valve case controllers (CC100Ps) and liquid-side stepper valve case con- trollers (CC100LSs) in this field.

Suction Controllers (CC100H) Enter the num- ber of suction stepper case controllers (CC100Hs) in this field.

Circuit Suction (CS100) Enter the number of suc- tion lineup circuit controllers (CS100s) in this field.

10-16 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Page 128
Image 128
Emerson E2 operation manual Set Up Echelon Net Work, Checking Online Status, Specifying Number Devices