Alarm Name

Default

Definition

Priority

 

 

 

 

 

External Fault

30

An external fault input defined in a Multiflex PAK

 

 

controller has indicated a failure. External fault

 

 

inputs in the PAK are used to detect a Rack (Pack)

 

 

failure produced by some device out of the PAK's

 

 

control.

Failed Attempt To Bind Input

50

A valid link could not be made between an E2 appli-

 

 

cation and an input assigned to it.

Failed Sensor Or Bad Wiring

20

E2 is unable to get a valid sensor value due to a possi-

 

 

ble hardware problem.

Failed To Create logging

20

E2 is unable to create logs for the input or output

 

 

shown.

Failed to Obtain DHCP Lease

20

Failed to obtain a DHCP lease from the DHCP

 

 

Server, when a lease is requested. This happens at

 

 

system startup, if a DHCP lease is requested, or if the

 

 

user switches to using DHCP.

Failed to Renew DHCP Lease

20

DHCP Lease failed to renew altogether. DHCP

 

 

Leases are renewed at an interval of half the time of

 

 

the requested lease. If the lease is for 5 days, then a

 

 

renewal will happen at 2.5 days. If this fails, it will

 

 

retry at the ¾ of the lease time. If both attempts fail,

 

 

the alarm is generated.

Fax Init String Is Not Valid

30

The fax initialization string for the E2’s modem is

 

 

incorrect and may need editing.

Features denied during restore

99

License manager has denied permission to access a

 

 

feature during a restore. Either the license for that

 

 

feature is invalid or it does not exist, or the number of

 

 

licenses for that feature is less than the number

 

 

needed for the configuration. Further information

 

 

may be found in the service log.

Features denied during startup

99

License manager denied permission to access a fea-

 

 

ture during startup. Either the license for that feature

 

 

is invalid or it does not exist, or the number of

 

 

licenses for that feature is less than the number

 

 

needed for the configuration. Further information

 

 

may be found in the service log.

File Not Found

50

An internal error has occurred in the E2.

Firmware File Bad - AI200

15

A 16AIe has corrupted firmware.

Firmware File Bad - RO200

15

An 8ROe has corrupted firmware.

Firmware File Bad - CC100 Liq

15

A CC-100P or CC-100LS has corrupted firmware.

Firmware File Bad - CC100 Suct

15

A CC-100H has corrupted firmware.

Firmware File Bad - CS100 Ckt

15

A CS-100 has corrupted firmware.

Firmware File Bad - ESR8

15

An ESR8 has corrupted firmware.

Firmware File Bad - RT100

15

An RT-100 has corrupted firmware.

C-6 E2 RX/BX/CX I&O Manual

026-1610 Rev 13 14-SEP-2011

Page 228
Image 228
Emerson E2 operation manual Alarm Name Default Definition Priority