
OCX 8800
Instruction Manual
Total Power Loss
In the event that the OCX 8800 will not power up at all, check the incoming power supply to make sure power is being delivered to the OCX 8800. If the incoming power supply is good, then check fuses F1 and F6 in the electronics housing. Refer to Figure
Figure 8-1. Fuse Locations
F6
Neutral (N)
10 Amp, 250 VAC
F1
Line (L1)
10 Amp, 250 VAC
F3
O2 and COe Heater
4 Amp, 250 VAC
F4
Sample Block Heater
8 Amp, 250 VAC
37390050
DIAGNOSTIC ALARMS
Always install a blocking diode on the customers relay coil. Failure to install a blocking diode may create noise spikes and cause faults in the OCX electronics.
The OCX 8800 is equipped with a set of alarm relay contacts on the microprocessor board in the electronics housing. This set of dry contacts can be connected to any customer supplied relay device, 30 VDC, 30 mA maximum. A blocking diode is required on the customers relay coil.
Any fault condition in the OCX 8800 will trip the alarm relay. The optional SPA with HART programmable alarm indicates LOW O2, HIGH COe, Calibration Status, and Unit Failure. For more information refer to Appendix B - SPA with HART Alarm.