OCX 8800

Instruction Manual

IM-106-880, Rev 1.0 January 2007

Figure B-6. SPA Configuration Menu for OCX 8800 Communication

SET

HART

SGNL SRCE

FLT

SRCE

CONF OPTS

SET EGU

SCLE INPT

￿SET MSTR ￿ ￿ PRIM

￿SET FUCT ￿ ￿ NRML

￿NUM VARS ￿ ￿ 02

￿NUM TRYS ￿ ￿ 03

￿EXIT HART ￿ SGNL SRCE

￿AOUT SRCE ￿ ￿ SV

￿AL2 SRCE ￿ ￿ PV

￿AL3 SRCE ￿ ￿ PV

￿AL4 SRCE ￿ ￿ PV

￿EXIT SRCE ￿ FLT SRCE

￿CONF OPTS

￿SET LINR ￿ ￿ LINR OFF

￿PV SCLE ￿ ￿ AUTO

￿DSPL EGU ￿ ￿ CSTM ￿ ￿ PPM (select P, select P, select M)

￿DSPL SRCE ￿ ￿ SV

￿AL2 SEL ￿ AL2 FLT

￿SET FAIL ￿ FAIL LOW

￿EXIT OPTS ￿ SET EGU

￿PV EGU ￿ ￿ PCT

￿SV EGU ￿ ￿ CSTM ￿ ￿ PPM (select P, select P, select M)

￿EXIT EGU ￿ SCLE INPT

￿PV SCLE ￿ PV ZERO ￿ 0000 PCT

￿PV FULL ￿ 25 PCT

￿SCLE SV ￿ SET ZERO ￿ 0000 PPM

￿SET FULL ￿ 1000 PPM

￿EXIT SCLE ￿ SCLE DSPL

SCLE INPT

 

 

 

￿ PV DSPL

SCLE

￿ SET ZERO ￿ ￿ 0000 PCT

DSPL

￿ SET FULL ￿ ￿ 25 PCT

 

 

 

￿ SV DSPL

 

 

 

￿ SET ZERO ￿ ￿ 0000 PPM

 

 

 

￿ SET FULL ￿ ￿ 1000 PPM

 

 

 

￿ EXIT DSPL ￿ SCLE OUT

 

 

 

￿ SET ZERO ￿ ￿ 4.000 MA

SCLE

￿ SET FULL ￿ ￿ 20.00 MA

OUT

￿ EXIT Z/FS

 

 

 

￿ TRIM OUT

 

 

 

￿ TRIM ZERO ￿ ￿ 4.000 MA

TRIM

￿ TRIM FULL ￿ ￿ 20.00 MA

OUT

￿ EXIT TRIM ￿ CONF ALRM

 

 

 

Refer to

 

 

 

CONF

SPA manual

ALRM

for settings or

 

 

 

￿ PASS WORD

 

 

 

 

 

 

￿ CONF EXIT

PASS

WORD

 

 

￿ SPA setup complete;

 

 

 

CONF

EXIT

observe process value display.

 

SCLE DSPL

37390003

B-6

Page 162
Image 162
Emerson OCX 8800 instruction manual Scle