The branch circuit to be installed on the customer’s power distribution panel must be a circuit breaker (CB) in compliance with the requirements in Table 5-5. In addition, follow the guidelines below.

Do not connect other electrical devices to this branch circuit.

Total load of the branch circuit must be under 80–90 percent of the rating.

Prepare a backup circuit to the power distribution panel based on possible device

￿additions in future.

Locate the device as close as possible to the power distribution panel for ease of maintenance.

Table 5-5 Requirements for Circuit Breaker on Power Distribution Panel

Router Model

 

AC Input

 

DC Input

 

 

 

 

 

 

 

 

CB Type

Phase

Rating

CB Type

Phase

Rating

GR2000-2S

15AT

Single

100 V ac, 15A

 

 

 

 

 

 

 

 

 

 

 

15AT

Single

200 V ac, 15A

 

 

 

 

 

 

 

 

 

 

GR2000-4S

15AT

Single

100V ac, 15A

 

 

 

 

 

 

 

 

 

 

 

15AT

Single

200V ac, 15A

 

 

 

 

 

 

 

 

 

 

Page 306
Image 306
Hitachi GR2000 manual Requirements for Circuit Breaker on Power Distribution Panel