Power cord

Required power cord (supplied with printer):

 

North American (UL/CSA approved), length 8.2

 

feet (2.5 m), OR

 

European (Harmonized), length 8.2 feet (2.5 m)

 

 

Ventilation

The printer uses solvent-based inks. The printer

 

does not include an integrated exhaust hood or

 

shielding for collecting the volatile organic com-

 

pound (VOC) emissions from the inks and

 

cleaning solvent. The owner is responsible for

 

ventilation and VOC recovery as required by

 

local regulations. Connection kits are available

 

from MacDermid ColorSpan to vent VOC emis-

 

sions to the customer’s exhaust system or VOC

 

recovery equipment. Consult your MacDermid

 

ColorSpan reseller for details.

 

The air surrounding the printer should be

 

changed every 1-3 minutes or as desired to

 

reduce or remove the solvent odor. The greater

 

the amount of printing, and the larger the room

 

in which the printer is located, the larger the

 

fan required to change the air at a given rate.

 

The space volume can be reduced with an

 

enclosure around the printer or by moving the

 

printer to a smaller room. Examples:

 

Cubic feet per minute (CFM) (typical) to

 

change the air in 3 minutes/1 minute:

 

Enclosure (4x10x6 feet): 80/240 CFM

 

Small Room (10x12x8 feet): 320/960 CFM

 

Medium Room (10x20x8 feet): 533/1600 CFM

 

Select a fan with a CFM rating at or greater than

 

the calculated CFM. The actual CFM required

 

will vary with local building and airflow condi-

 

tions.

 

 

Operating

68–85° F (20–30° C)

Conditions

20–80%, non-condensing

 

 

Approvals

Safety: UL, c-UL, CE

 

Emissions: FCC-A, CE

 

Immunity: CE

 

 