Intel® Server System SR1520ML User’s Guide 45
9. Set the replacement fan into place. See letter “A” in the following figure. When
correctly positioned, the fan cable extends from the top right side of the fan, at the
rear.
10. Install the screws you removed in step 7 to secure the fan to the bracket. See letter
“B” in the figure.
11. Connect the fan cable at the Y-connector. See letter “C”
12. If you removed the main power cable, b undle the fan cables together and hold them
in place under the cable for the main power cable while you connect the main
power cables. Use caution to make sure you do not pinch any cables when you
connect the main power supply connectors. Make sure the fan cables will not block
airflow from the memory cooling fans. See letter “D”
Figure 36. Connecting Memory Cooling Fan Cable
13. Install the processor air duct. For instructions. see “Installing the Processor Air
Duct” on page 29.
AF002504
BA
D