Product Description
4

1.3.3 Removing Piano Jacks

Once the unit has been moved to the installation location, Emerson Network Power recommends
using the following method to remove the piano jacks.
1. Lower the unit as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Remove all cushioning material that might have been used to protect the unit panels from the
strapping and/or the piano jacks.
4. Use a pry bar or similar device on one side of the unit, lift unit just enough to allow for the
removal of the piano jack.
5. Repeat the previous step to remove the piano jack on the opposite side.
6. Remove the plastic bag.
1.4 Mechanical Considerations

1.4.1 Positioning the Liebert XDC

Install the Liebert XDC according to the site specific documentation and secure the unit to the floor.
The Liebert XDC can be installed near a wall or another Liebert XDC. However, there must be at
least 3 feet (92cm) clearance in front of the Liebert XDC as service access for components in the unit.
Figure 5 Dimensional data
NOTE
During installation of the Liebert XDC, the top, bottom, front and left side of the unit
must be accessible.
Table 1 Liebert XDC dimensions, weight
Air Cooled
Model Dimensional Data, inches (mm) Shipping Weight, lb (kg)
50/60Hz A B * C D E Domestic Export
XDC160 74 (1880) 34 (864) 33-1/8 (841) 33 (838) 7 2 (1829) 1945 (882) 2093 (949)
*Dimension does not include the bezel of the disconnect switch.
C
D
B
Overall
5"
(127mm)
17"
(432mm)
1"
(25.4mm)
2"
(51mm)
78"
1981mm
A
Overall
Shaded areas indicate a
recommended clearance
of 34" (864mm) for
component access.
D
Unit
Base
E
Unit Base

Unit Dimensional Data

Floor Cutout Dimensions

DPN000768

Page 2, Rev. 6

Recommended
Minimum Hot Gas
Supply & Liquid Return
Piping Opening