Piping and Filling with Refrigerant:
2.0PIPING AND FILLING WITH REFRIGERANT:
2.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases
The
Refer to the full regulation for additional details.
2.2Recommended Pipe Size
NOTE
Follow all local codes on maximum length and size of refrigerant lines.
Connect the main pipes between the Liebert XDC and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions shall be minimized for proper operation.
Table 4 | Supply, return pipe sizes for Liebert XD refrigerant loop | |
|
|
|
| Pipe Function | Size/Equivalent Pipe Length |
Liebert XDC supply line, from Liebert XDC | ||
supply to farthest Liebert XD cooling module | ||
Liebert XDC return line, from farthest cooling | ||
module to Liebert XDC return | ||
From any model Liebert XDO/Liebert XDH | 1/2" OD (0.430" ID) for lengths up to 10 feet | |
supply to supply line of Liebert XDC | 7/8" OD (0.785" ID) for lengths over 10 but less than 25 feet | |
From any model Liebert XDO/Liebert XDH | 7/8" OD (0.785" ID) for lengths up to 10 feet | |
return to return line of Liebert XDC | ||
From any model Liebert XDV/Liebert XDCF | 1/2" OD (0.430" ID) for lengths up to 10 feet | |
supply to supply line of Liebert XDC | 5/8" OD (0.545" ID) for lengths over 10 but less than 35 | |
From any model Liebert XDV/Liebert XDCF | 5/8" OD (0.545" ID) for lengths up to 10 feet | |
return to return line of Liebert XDC | 7/8" OD (0.785" ID) for lengths over 10 but less than 35 feet |
2.3Liebert XDC Interconnection With Liebert XD Cooling Module
All piping must be ASTM (American Society for Testing and Materials) Type “L” copper pipe.
The Liebert XDC may be connected to Liebert XD cooling modules with either Liebert’s XD prefabri- cated piping assembly or with rigid,