Specifications
Table 28 Floor stand
Models - 60 Hz | XDC160 Glycol Floor Stand - 60Hz - 40% EG | ||||
Outside Ambient °F (°C) | 95 (35) |
| 100 (38) |
| 105 (41) |
|
|
|
|
|
|
Entering Fluid Temp °F (°C) | 110 (43) |
| 110 (43) |
| 110 (43) |
|
|
|
|
|
|
Performance Data |
|
|
|
|
|
Cooling capacity, tons (kW) |
| 42.5 (149.4) |
| ||
|
|
|
|
| |
Total Heat Rejection, (kW) |
| 192.6 |
|
| |
|
|
|
|
| |
Flow, GPM |
| 204 |
|
| |
|
|
|
| ||
Pressure Drop, psi (ft water) |
| 35.9 (82.9) |
| ||
|
|
|
|
|
|
Heat Rejection Equipment |
|
|
|
|
|
Drycooler | DNT 940A |
| 2 x DNT 880A* | ||
|
|
|
|
| |
Drycooler Pressure Drop, psi (ft water) |
| 6.5 (15.1) |
| 2.7 (6.3) | |
|
|
|
|
|
|
Glycol pump package - 10HP |
|
| 9A31258G3 |
| |
|
|
|
|
| |
Pump Control Package - 208V |
|
| 9A34606G47 |
| |
|
|
|
|
| |
Pump Control Package - 460V |
|
| 9A32114G4 |
| |
|
|
|
|
| |
Pump Total Head @ 204 GPM, ft water |
| 145 |
|
| |
|
|
|
|
| |
Water regulating valve size |
|
|
| ||
|
|
|
|
|
|
Piping Connections |
|
|
|
|
|
Water / glycol supply and return lines |
|
|
| ||
|
|
|
|
|
|
* When multiple drycoolers are used ensure flow is balanced.
56