Specifications

Table 28 Floor stand specifications—Liebert XDC with 40% ethylene glycol

Models - 60 Hz

XDC160 Glycol Floor Stand - 60Hz - 40% EG

Outside Ambient °F (°C)

95 (35)

 

100 (38)

 

105 (41)

 

 

 

 

 

 

Entering Fluid Temp °F (°C)

110 (43)

 

110 (43)

 

110 (43)

 

 

 

 

 

 

Performance Data

 

 

 

 

 

Cooling capacity, tons (kW)

 

42.5 (149.4)

 

 

 

 

 

 

Total Heat Rejection, (kW)

 

192.6

 

 

 

 

 

 

 

Flow, GPM

 

204

 

 

 

 

 

 

Pressure Drop, psi (ft water)

 

35.9 (82.9)

 

 

 

 

 

 

 

Heat Rejection Equipment

 

 

 

 

 

Drycooler

DNT 940A

 

2 x DNT 880A*

 

 

 

 

 

Drycooler Pressure Drop, psi (ft water)

 

6.5 (15.1)

 

2.7 (6.3)

 

 

 

 

 

 

Glycol pump package - 10HP

 

 

9A31258G3

 

 

 

 

 

 

Pump Control Package - 208V

 

 

9A34606G47

 

 

 

 

 

 

Pump Control Package - 460V

 

 

9A32114G4

 

 

 

 

 

 

Pump Total Head @ 204 GPM, ft water

 

145

 

 

 

 

 

 

 

Water regulating valve size

 

1-1/4"

 

 

 

 

 

 

 

 

Piping Connections

 

 

 

 

 

Water / glycol supply and return lines

 

2-5/8"

 

 

 

 

 

 

 

 

* When multiple drycoolers are used ensure flow is balanced.

56

Page 62
Image 62
Liebert XDC user manual 204