Product Description

Figure 6 Piping locations

** To first cooling module or bypass flow controller

F - Return From Cooling Units

Install replaceable filter dryer assembly in liquid supply line G

* Orientation determined by installer.

47"

G - Supply to Cooling Units

44"

(1193.8mm)

(1117.6mm)

6" (152mm)

23"

(584.2mm)

Dimensions are approximate and subject to change without notice.

A - Hot GasB - Liquid

Refrigerant Lines

* Allow 8" (204mm) of clearance for filter replacement

Refrigerant Lines

**To ensure all refrigerant flow is filtered, install the filter dryer assembly

between the discharge line of the Liebert XDC and the first bypass flow controller or the first cooling module.

Table 2 Liebert XDC piping connection sizes

DPN000768 Page 3, Rev. 6

Air Cooled Model

 

Piping Outlet Connection Sizes, OD Cu, inches

 

 

 

 

 

 

 

 

 

50/60Hz

A

B

C

D

E

F

G

 

 

 

 

 

 

 

 

XDC160

1-3/8

7/8

-

-

-

2-1/8

1-1/8

 

 

 

 

 

 

 

 

5

Page 11
Image 11