Product Description
1.0PRODUCT DESCRIPTION
1.1General Product Information
1.1.1Product/System Description
The Liebert XDC™ (eXtreme Density Chiller) is
The Liebert XDC monitors room conditions and prevents coil condensation by maintaining the coolant being pumped to the cooling modules at a temperature above the room dew point. All functions, such as temperature control, switching pumps (if necessary), etc., are automatic.
The Liebert XDC’s minimum recommended operating load is 40% of system nominal capacity. For example, a Liebert XDC160 60Hz system’s minimum load would be 64 kW. Loading below this value can unfavorably affect system operation. Consult factory for any loading below this recommendation.
See Table 25 for the Liebert XDC160 rated cooling capacity.
Figure 1 Liebert XDC components
Condenser | Liebert XDC | Liebert XD Cooling Modules | |
Compressor | |||
| |||
Unit |
| ||
|
| ||
| Heat Exchanger | Pumps | |
| Receiver |
1.2Equipment Inspection
When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.
1.3Equipment Handling
! WARNING
Risk of unit falling over. Can cause death, injury and equipment damage.
The Liebert XDC is
1