Troubleshooting
7.0TROUBLESHOOTING
Table 24 Liebert XDC troubleshooting
Symptom | Possible Cause | Check or Remedy | |
|
|
| |
| No main power | Check L1, L2, and L3 for rated voltage. | |
|
|
| |
Pump/compressor | Loose electrical connections | Tighten connections. | |
|
| ||
Overloads tripped | Allow pump to cool. Check amp draw. | ||
will not energize | |||
|
| ||
| Tripped circuit breaker | Check circuit breaker to pump(s). | |
|
|
| |
| Incorrect phase wiring | See Table 18. | |
|
|
| |
| Isolation valve(s) on pump suction | Open all isolation valves completely during normal operation. | |
| and/or discharge is closed. | ||
|
| ||
| Liebert XD cooling modules are Off. | Check Liebert XD cooling modules to make sure that they are | |
| ON prior to starting the Liebert XDC | ||
|
| ||
|
| Check alarm(s) history on Liebert XDC. The Liebert XDC was | |
|
| operating below the dew point for a significant amount of | |
| Low Refrigerant Temperature | time. Check humidity in conditioned space; lower humidity if | |
| (high dew point) | necessary to allow Liebert XDC to operate at a lower | |
Pump will not run |
| temperature. (Disconnect must be switched to Off then back | |
| to On to allow Liebert XDC to reset.) | ||
| Incorrect location of | Place the sensor on the return air side of the primary air | |
| mover (I.e., Liebert Deluxe System 3). Do not install the | ||
| |||
| sensor near unsealed doors, windows and similar areas. | ||
|
| ||
|
|
| |
|
| Check both differential pressure settings. If not within 6 psi, | |
| Pressure switch not making contact | ±1 psi (41 kPa, ±7kPa; 0.41 bars, ±0.07 bars) then manually | |
|
| change accordingly. | |
| Not enough charge | See 2.7 - Filling the Direct Expansion (DX) | |
| 407c. | ||
|
| ||
|
| Check for adequate charge in system, refer to the user | |
| Cavitation due to vapor in pump | manual. 2.7 - Filling the Direct Expansion (DX) | |
Pump noisy |
| 407c | |
| Pump is rotating in reverse | See Table 18 | |
|
|
| |
| Worn motor bearings | Replace pump | |
|
|
| |
| Low Refrigerant Temperature | Check humidity of room along with location of remote | |
| sensors. Make sure that the sensors are not located in a cold | ||
| (high dew point) | ||
| area where there is a lack of sufficient air flow. | ||
|
| ||
|
|
| |
Liebert XDC (Pump) | Loss of power | When power is restored, the Liebert XDC will automatically | |
suddenly stops |
| restart. | |
| Clogged filter/dryer and/or impeller | Clean out debris. | |
|
|
| |
| Leak in system - loss of charge | Check the entire system for leaks with a refrigerant sniffer. | |
| Repair as necessary. | ||
|
| ||
| Lack of load in the room | If there is no cooling required, turn the Liebert XDC off at the | |
| I/O button. | ||
|
| ||
Room becomes | Minimum room temperature setpoint | Check the setpoint by following instructions in 5.3.2 - | |
is too low. | SETPOINTS. | ||
too cold | |||
| Incorrect location of temperature- | Place the sensor on the return air side of the primary air | |
| mover (i.e., Liebert Deluxe System 3). Do not install the | ||
| humidity senors. | ||
| sensor near unsealed doors, windows, and similar areas. | ||
|
| ||
|
|
| |