Microprocessor Control

PUMP OFF TD

The user can set the amount of time a pump will remain off when refrigerant flow is interrupted or stops. After the time delay has expired, the control will try to restart the pump (see PUMP START TD).

LEAD PUMP

This allows the user to select which pump is the active pump. It can be set to PUMP 1 or PUMP 2. The control will operate the respective pump unless a loss of flow condition occurs. On a LOSS OF FLOW condition, the control will switch to the standby pump after the LOSS OF FLOW alarm time delay has elapsed and the LOSS OF FLOW alarm has been annunciated. The default is PUMP 1.

LEAD TANDEM

Not currently used.

DIPSWCH

This allows the user to read the eight-position DIP switch located on the control board. The switches are numbered according to the numbers on the DIP switch. The numeral 1 indicates the switch is ON and a 0 indicates the switch is OFF. These switches are factory-set and should not require any user changes.

Table 23 Liebert XDC DIP switches and factory settings

DIP Switch

Factory Setting

1

Off

2

Off

3

Off

4

Off

5

Off

6

Off = Standard, On = Dual Source

7

Off

8

Off

VALVE TIME

Valve travel time is not currently used.

VLV ST OPEN

Valve start open % is not currently used.

VLV START TD

Valve start time delay is not currently used.

MIN VLV SET

Minimum valve setpoint is not currently used.

COMP SEQ ON

When the Liebert XDC is started, this is the time delay before the next compressor comes on when the control is sequencing on compressors.

COMP OFF TD

This is how long a compressor must be off before the control will turn it back on.

INNERSTAGE TD

This is how long the control must wait between compressor stage changes during normal operation.

WSK1 TD

Compressor winter start kit time delay for all compressors.

WSK2 TD

The winter start kit 2 time delay is not currently used.

100% START TD

This is how long the control will keep the unit at 100% cooling during startup after all compressors have staged on.

41

Page 47
Image 47
Liebert XDC Pump OFF TD, Lead Pump, Lead Tandem, Dipswch, Valve Time, VLV ST Open, VLV Start TD, Min Vlv Set, Comp SEQ on