Piping and Filling with Refrigerant:
Figure 27 General arrangement air cooled Liebert XDC Lee-Temp Control
Condenser Coil
Inverted Trap * on discharge line to extend above base of coil by a minimum of
Check
Head Pressure Valve
Control with
Integral Check
Valve
Receiver
Additional
Piping
Assembly **
Rotalock
Valve **
1/4" (6.4mm) Pressure Relief Valve **
Traps * every 25 ft. (7.6m) of rise on hot gas line only
Return
LiquidCondenser
from
Sight Glass
Some Models
Have 2 Sight Glasses
Standard Piping
Assembly **
Single XDC Circuit Shown
Liquid/Return
Hot Gas/Discharge
*Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance.
** Components supplied by Liebert and must be
DPN000937 Pg. 4, Rev 9
Table 12 Recommended refrigerant line sizes, DX R-407c, OD copper
Liebert XDC 160
Equivalent | *Hot Gas Line, |
|
Length, ft., (m) | in. | Liquid Line, in. |
|
|
|
50 (15) | 7/8 | |
|
|
|
100 (30) | ||
|
|
|
150 (45) | ||
|
|
|
200 (60) | ||
|
|
|
*Double risers are required when hot gas vertical rise is 15 feet or more (see 2.6 - Install Double Discharge Risers).
27