Piping and Filling with Refrigerant:
2.7Filling the Direct Expansion (DX) Circuit—R-407c
NOTE
If necessary, refer to 3.0 - Installation Checklist to ensure that the system has been properly checked out and is ready to be filled with coolant.
Any recommended volumes will be approximate. The user must verify that all circuits of the system have been adequately filled.
For Air Cooled
NOTE
Proper safety equipment and proper refrigeration tools are required. Check unit nameplate for correct refrigerant type before topping off or recharging a system.
NOTE
Refrigerant
Refrigerant
1.Make sure the Liebert XDC is Off.
2.Connect the refrigerant gauge charging hose to the refrigerant drum and to the receiver at the rotalock valve and/or to the Schrader valves on the liquid lines.
3.Weigh in the calculated charge based on Tables 14, 15, 16 and
4.Open the rotalock valve and fill the complete calculated charge.
Table 14 Indoor unit refrigerant charge—R-407c
Model 50/60 Hz | Charge/Circuit, lb. (kg) |
|
|
Liebert XDC160 | 17.5 (8.0) |
|
|
Table 15 Outdoor air condenser charge—R-407c
Outdoor Ambient, °F (°C | Model 50/60 Hz | Charge / Circuit, lb (kg) |
CDL830 or CSL415 | 200 (90.8) | |
|
|
|
CDL830 or CSL415 | 200 (90.8) | |
|
|
|
CSL616 | 254 (115.2) | |
|
|
|
35 to 105 (2 to 41) | CSL616 | 164 (74.5) |
|
|
|
Table 16 Air cooled systems - liquid line charge -
O.D., inches | Liquid Line, lb (kg) | Hot Gas Line, lb (kg) | |
3/8 | 3.7 | (1.7) | - |
1/2 | 6.9 | (3.1) | - |
5/8 | 11.0 (5.0 | 2.2 (1.0) | |
3/4 | 15.7 (7.1) | 3.1 (1.4) | |
7/8 | 23.0 | (10.4) | 4.5 (2.0) |
39.3 | (17.8) | 7.8 (3.5) | |
59.8 (27.1 | 11.8 (5.4) | ||
| - | 16.7 (7.6) |
Table 17 Indoor water/glycol cooled module – R-407C refrigerant charge
Model 60 Hz | Charge / Circuit, lb(kg) |
|
|
Liebert XDC 160 | 30.0 (13.2) per circuit |
|
|
31