Microprocessor Control
5.3.16CUSTOM TEXT
This menu permits the user to set up a custom text message with a maximum length of 16 characters. The message may use any of the following characters or a blank space:
ABCDEFGHIJKLMNOPQURSTUVWXYZ#%*-0123456789.
This custom text can be designated as the custom alarm text in the CUSTOM ALARMS menu (see CUSTOM ALARMS above). To define the message:
1.Press the ENTER button to access the menu.
2.Use the up or down arrow key to change the character with the pointer below it.
3.Press the ENTER button to go to the next character.
4.Repeat the steps for all characters in the message (maximum of 16 characters).
5.Press the ENTER button to accept new custom text.
5.3.17DIAGNOSTICS
This allows the user to perform checks on inputs, outputs, and conduct a test of the Liebert XDC con- trol board from the wall box.
Entering the TEST OUTPUTS will interrupt system operation. Selecting TEST INPUTS or TEST MICRO will not interrupt system operation. Pressing ENTER and selecting TEST OUTPUTS will permit the user to toggle the following outputs on and off:
PUMP
COMP 1A, 2A, 1B,
LLSV1, LLSV2—On/Off
HGSV1, HGSV2—On/Off
HGV1, HGV2—On/Off
DEHYDRATION1,
Pressing ENTER and selecting TEST INPUTS will permit the user to read the following inputs:
INPUT
Pressing ENTER and selecting TEST MICRO will permit the user to test the microcontroller and associated circuitry on the Liebert XDC control board.
45