Troubleshooting

Table 24 Liebert XDC troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy

 

Liebert XDC is off.

Check status of the Liebert XDC at the user interface. Turn

 

system On at I/O button if system is Off.

 

 

 

 

Check temperature and relative humidity (RH) of room.

 

High dew point

Lower RH setpoint if necessary to lower dew point. At normal

 

room temperature of 68°F (20°C), the RH should be set to

 

 

Room becomes

 

50% or lower.

 

 

Liebert XD cooling modules are Off.

Check Liebert XD cooling modules to make sure that they are

too warm

On before starting the Liebert XDC.

 

 

 

 

 

 

Minimum room temperature setpoint

Check the setpoint by following instructions in 5.3.2 -

 

is too high.

SETPOINTS.

 

Incorrect location of temperature-

Place the sensor on the return air side of the primary air

 

mover (I.e., Liebert Deluxe System 3). Do not install the

 

humidity senors

 

sensor near unsealed doors, windows, and similar areas.

 

 

 

 

 

Pipe rattle

Loose pipe connections

Check pipe connections.

 

 

 

 

No 24VAC power to motor

Check for 24VAC between P2-1 and P2-4.

 

 

 

Actuator motors

No signal from control

Check 24VAC at P22-1 (close) or P22-3 (close).

 

 

 

Unplug P22 completely off of the board. Jumper P22-5 to P2-

(if applicable)

 

Motor not operating

4 for grounding, then jumper P22-1 to P2-1 to drive close.

 

 

Remove jumper to close, and then jumper P22-3 to P2-1 to

 

 

 

 

drive open. If motor fails to work, replace it.

 

 

 

 

Check control panel for welded

 

Motor burnout

contactor contacts or welded

Replace defective components.

 

overload contacts

 

Main 24VAC

Shorts or loose connections

Check the wiring connections of the 24VAC circuit.

fuse trips

Faulty circuit board

Replace the circuit board.

 

 

 

Unstable pump

R-134a pump loop is overcharged

While pump is running R-134a receiver level must be within

operation

recommended levels (see Figure 31).

 

51

Page 57
Image 57
Liebert XDC user manual Too warm