Piping and Filling with Refrigerant:
2.5Filling the Pumped Circuit—R-134a
1.Connect a charging manifold to the service port of the receiver outlet valve.
2.Purge the hoses.
3.Calculate the amount of
4.Weigh in the calculated charge.
5.After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium. Observe the refrigerant level through the sight glasses of the receiver. The level should be above the second sight glass at a minimum when the Liebert XDC is off.
6.If the refrigerant level is improper, the charge must be adjusted.
If the level is too high or too low, recalculate the required charge and reduce or increase the amount as needed to reach the proper level.
NOTE
All lengths in Tables 7, 8 and 9 are actual pipe lengths, not equivalent pipe lengths.
NOTE
System refrigerant volume calculations derived from Tables 6, 7, 8 and 9 are based on a fully loaded system. Additional charge may be required for lightly loaded systems.
Table 6 System
Refrigerant Charge, | Per Liebert XD Unit |
(Excludes Connector Lines | |
lb (kg) | to and from Liebert XD Cooling Module) |
157 lb. (65.7kg) | Liebert XDC |
|
|
3.55 lb. (0.66kg) | Liebert XDO |
|
|
2.32 lb. (1.05kg) | Liebert XDV |
|
|
5.32 lb. (2.41kg) | Liebert XDH |
|
|
1.41 lb. (0.64kg) | Liebert XDCF |
|
|
Table 7 System refrigerant charge for the supply and return mains
Refrigerant Charge, |
|
lb/foot (kg/m) | Supply/Return Main Length and Diameter |
0.45 (0.67) | Main supply actual length per |
|
|
0.68 (1.01) | Main supply actual length per |
|
|
0.28 (0.42) | Main return actual length per |
|
|
0.43 (0.64) | Main return actual length per |
|
|
Table 8
Refrigerant Charge, |
|
lb/foot (kg/m) | |
|
|
0.08 (0.12) | 1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF supply connector actual length |
|
|
0.13 (0.19) | 5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length |
|
|
0.26 (0.39) | 7/8" OD Liebert XDO/Liebert XDH supply connector actual length |
|
|
0.02 (0.03) | 5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length |
|
|
0.04 (0.06) | 7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length |
|
|
0.04 (0.06) | 7/8" OD copper tubing Liebert XDH/Liebert XDO return connector actual length |
|
|