Piping and Filling with Refrigerant:
2.6.1Air Cooled Condenser with
The
Lee-Temp Piping
Two discharge lines and two liquid lines must be
Lee-Temp Control Materials Supplied
•
•Air cooled condenser
•Piping access cover to be reinstalled when piping is complete
•
•Terminal block for
•Condensate
•
•
•Insulated storage
•Head pressure control assembly (head pressure valves and check valves) - one per circuit
•Service
•Pressure relief
•Liquid level sight glasses
NOTE
Evacuation and Leak
1.Make sure the unit is Off. Open all disconnects and pull all fuses except the control fuses. On units supplied with circuit breakers, open all breakers except for the transformer.
2.Energize the liquid line solenoid valves via 24VAC or through Diagnostics under “Test Outputs,” select DEHYDRATION to be On (see 5.3.17 - DIAGNOSTICS). This will energize the solenoids and hot gas valves to open simultaneously on Circuit 1 and Circuit 2.
NOTE
The procedures above allow the technician to use 24VAC power and controls to open liquid line solenoid valve(s) for the dehydration process. If no power is at the unit disconnect, the technician is to use a separate 24VAC source rated at 75 VA and connect to the system liquid line solenoid valve(s) directly.
3.Attach refrigerant gauges to the suction and discharge service valves of the compressor.
4.Open all compressor service valves, including those located outside the Liebert XDC.
5.Connect the tank of dry nitrogen to the Schrader valves on the liquid lines and the hot gas lines.
6.Pressurize the system circuit(s) to 150 PSIG (1034 kPa; 10.34 bars) with dry nitrogen with a trace of refrigerant. Check the system for leaks with a suitable leak finder.
7.After completion of leak testing, release the test pressure (per local code) and connect to vacuum pump(s) at the Schrader valves on the liquid lines and on the hot gas lines.
8.After 4 hours of pulling a deep vacuum, check the vacuum levels and, if they have not changed, break the vacuum with dry nitrogen.
9.Pull a second and third vacuum to 250 microns or less. Recheck the vacuum level after 2 hours.
30