Piping and Filling with Refrigerant: R-134a and R-407c Circuits

Figure 28 DCSL616 piping connections—two refrigerant circuits connected for parallel flow

Inverted Trap * on discharge line to extend above base of coil by a minimum of 7-1/2" (190mm)

Condenser Coil (Circuit 2)

Condenser Coil (Circuit 1)

Additional Piping Assembly **

Traps * every 25 ft (7.6m) of rise on hot gas line only

Head Pressure Control with Integral Check Valve

 

 

 

 

 

 

 

 

m

 

 

 

d

 

o

 

 

 

 

 

r

 

 

 

i

 

 

 

 

 

u

 

 

F

 

r

q

 

 

n

 

 

i

 

 

 

 

e

L

 

 

 

r

 

 

 

 

u

 

s

 

 

t

 

 

n

 

 

 

e

 

 

e

 

 

R

 

 

d

 

 

 

 

 

 

 

n

 

 

 

 

 

 

o

 

 

 

 

 

 

C

 

 

 

 

 

 

 

Rotalock

Check

Valve **

 

Valve

1/4" (6.4mm)

 

 

Pressure Relief

Lee-Temp

Valve **

 

Receiver

Sight Glass

 

Some Models Have

2 Sight Glasses

Standard

Piping Assembly **

* Components are not supplied by Liebert

 

 

 

but are recommended for proper circuit

 

 

 

operation and maintenance.

 

 

Liquid/Return

* * Components supplied by Liebert;

 

must be field-installed.

 

 

 

 

 

 

Single XDC Circuit Shown

 

Hot Gas/Discharge

Field-Supplied Piping

DPN000937

 

 

 

Factory-Supplied Piping

 

 

 

Pg. 4, Rev 9

 

 

 

 

 

Table 13 Recommended refrigerant line sizes for DCSL616

 

 

 

 

 

 

 

 

Liebert XDC 160

 

 

 

 

 

 

 

 

 

Equivalent

*Hot Gas Line,

 

 

 

 

Length, ft., (m)

in.

 

Liquid Line, in.

 

 

50 (15)

1-1/8

 

7/8

 

 

 

 

 

 

 

 

100 (30)

1-1/8

 

1-1/8

 

 

 

 

 

 

 

 

150 (45)

1-3/8

 

1-1/8

 

 

 

 

 

 

 

 

200 (60)

1-3/8

 

1-1/8

 

 

 

 

 

 

 

 

*Double risers are required when hot gas vertical rise is 15 feet or more (see 2.6 - Install Double Discharge Risers).

28

Page 34
Image 34
Liebert XDC user manual Recommended refrigerant line sizes for DCSL616