Piping and Filling with Refrigerant: 
Figure 25 Installation data—Lee-Temp,  one-circuit,  high ambient six-fan  model
  | 
  | 
  | 
  | |||
* Liquid line from  | 
  | 
  | accordance with local codes or main unit  | |||
condenser  | 
  | 
  | 
  | switch ordered as optional equipment  | ||
(Circuit 1)  | 
  | 
  | 
  | |||
B  | 
  | 
  | 
  | 
  | 
  | |
* Hot gas line  | 
  | 
  | 
  | 
  | 
  | |
from unit  | 
  | 
  | 
  | 
  | 
  | |
(Circuit 1)  | 
  | 
  | 
  | 
  | 
  | |
5  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | 
  | 
  | 
  | ||
pad electric  | 
  | C  | 
  | 
  | 
  | |
box this end  | 
  | 
  | 
  | 
  | ||
(See DPN000937,Pg. 3)  | 
  | 
  | 
  | 
  | 
  | |
* Hot gas line to condenser (Circuit 1)  | 
  | 
  | 5  | Hot gas line  | Electrical service  | |
  | 
  | 
  | ||||
96" (2438mm) receiver  | 
  | 
  | 7  | (Circuit 1)  | by others  | |
shown; some systems  | 
  | 
  | Liquid return  | See Note 14  | Ensure piping stays  | |
use smaller receivers  | A  | D  | line to unit  | below electrical box  | ||
Liquid line  | ||||||
Position elbow to direct  | (Circuit 1)  | (Circuit 1) See Note 14  | and does not protrude  | |||
relief valve downward  | Metal  | 
  | Isolator  | See Page 5 for piping connection details  | |
Mounting Instructions  | Clamp  | 
  | |||
  | Note 14  | 
  | |||
1. Uncrate carton and inspect for damage to  | 
  | ||||
  | 
  | 
  | |||
condenser and condenser control panel.  | 
  | Materials Supplied by Liebert | |||
2. Assemble legs per instructions as shown.  | 
  | ||||
  | 1   | ||||
3. When piping long, vertical rises, oil traps are  | 
  | ||||
recommended on hot gas line every 25 ft. (7.6m)  | 
  | for details and field wiring.  | |||
(see 2.6 Install Double Discharge Risers).  | 
  | 2  | |||
4. Wire according to electrical diagram on inside  | 
  | 3 Piping access cover to be reinstalled when piping is  | |||
of condenser control box and in accordance with  | |||||
4   | |||||
all local codes.  | 
  | 
  | |||
5. All condenser locations more than 200 ft. (61m) of  | 
  | condenser frame.  | |||
equivalent piping length away from Liebert XDC unit  | 5   | ||||
must consult factory for special piping considerations.  | receiver. 3/8" nuts (10 total). 3/8" washers (20 total)  | ||||
6. Field to size refrigerant lines so as not to exceed  | 
  | ||||
6  | Terminal block for 2 wire 24 volt interlock connection  | ||||
2°F (1.1°C) saturation loss for total equivalent length  | |||||
(do not use connection sizes to determine line sizes).  | 
  | Liebert XDC unit and Liebert condenser.  | |||
7. Condenser installation is limited to a maximum of  | 7  | Condenser legs - (5) fivelegs for (6)   | |||
15 ft. (4.6m) location below Liebert XDC unit.  | 
  | 8  | |||
8. Do not run piping or wiring in the path of air flow  | |||||
  | a. Insulated storage receiver - storage  | ||||
as this will hamper the system performance.  | 
  | 
  | |||
  | 
  | receiver (1) per circuit. Receiver size varies.  | |||
9. Install   | 
  | 
  | |||
  | 
  | b. Dual head pressure control valve assembly  | |||
gas lines between condenser and field piping.  | 
  | 
  | |||
  | 
  | with integral check valve(s) - (1) one per circuit (S  | |||
10. All other piping   | 
  | ||||
  | c. Rotalock valve - (1) one per circuit,   | ||||
11. Inverted traps must be installed to allow proper  | 
  | 
  | |||
  | 
  | d. Pressure relief valve - (1) one per circuit,   | |||
clearance to fully open condenser control box door  | 
  | ||||
  | e. Liquid level indicator - (1) per circuit  | ||||
and in accordance with local electric codes.  | 
  | 
  | |||
12. Secure   | 
  | 
  | |||
condenser frame using hardware provided. Receiver  | 
  | DPN000937  | |||
can be mounted on either side of condenser.  | 
  | 
  | |||
  | 
  | Pg. 02, Rev. 09  | |||
13.   | 
  | 
  | |||
  | 
  | 
  | |||
assembly shipped loose for field installation.  | 
  | 
  | 
  | ||
Item C is shipped loose for field installation.  | 
  | 
  | 
  | ||
14. Fasten liquid and hot gas lines using flat  | 
  | See Figure 29 for details on piping connections. | |||
surface clamps with isolators (field provided).  | 
  | ||||
Support field piping separately to avoid coil damage and loss of charge.
15.Relieve pressure at access port. Replace access port fitting with relief valve before charging system.
25