Piping and Filling with Refrigerant:
Figure 25 Installation data—Lee-Temp, one-circuit, high ambient six-fan model
|
|
|
| |||
* Liquid line from |
|
| accordance with local codes or main unit | |||
condenser |
|
|
| switch ordered as optional equipment | ||
(Circuit 1) |
|
|
| |||
B |
|
|
|
|
| |
* Hot gas line |
|
|
|
|
| |
from unit |
|
|
|
|
| |
(Circuit 1) |
|
|
|
|
| |
5 |
|
|
|
|
| |
|
|
|
|
| ||
pad electric |
| C |
|
|
| |
box this end |
|
|
|
| ||
(See DPN000937,Pg. 3) |
|
|
|
|
| |
* Hot gas line to condenser (Circuit 1) |
|
| 5 | Hot gas line | Electrical service | |
|
|
| ||||
96" (2438mm) receiver |
|
| 7 | (Circuit 1) | by others | |
shown; some systems |
|
| Liquid return | See Note 14 | Ensure piping stays | |
use smaller receivers | A | D | line to unit | below electrical box | ||
Liquid line | ||||||
Position elbow to direct | (Circuit 1) | (Circuit 1) See Note 14 | and does not protrude |
relief valve downward | Metal |
| Isolator | See Page 5 for piping connection details | |
Mounting Instructions | Clamp |
| |||
| Note 14 |
| |||
1. Uncrate carton and inspect for damage to |
| ||||
|
|
| |||
condenser and condenser control panel. |
| Materials Supplied by Liebert | |||
2. Assemble legs per instructions as shown. |
| ||||
| 1 | ||||
3. When piping long, vertical rises, oil traps are |
| ||||
recommended on hot gas line every 25 ft. (7.6m) |
| for details and field wiring. | |||
(see 2.6 Install Double Discharge Risers). |
| 2 | |||
4. Wire according to electrical diagram on inside |
| 3 Piping access cover to be reinstalled when piping is | |||
of condenser control box and in accordance with | |||||
4 | |||||
all local codes. |
|
| |||
5. All condenser locations more than 200 ft. (61m) of |
| condenser frame. | |||
equivalent piping length away from Liebert XDC unit | 5 | ||||
must consult factory for special piping considerations. | receiver. 3/8" nuts (10 total). 3/8" washers (20 total) | ||||
6. Field to size refrigerant lines so as not to exceed |
| ||||
6 | Terminal block for 2 wire 24 volt interlock connection | ||||
2°F (1.1°C) saturation loss for total equivalent length | |||||
(do not use connection sizes to determine line sizes). |
| Liebert XDC unit and Liebert condenser. | |||
7. Condenser installation is limited to a maximum of | 7 | Condenser legs - (5) fivelegs for (6) | |||
15 ft. (4.6m) location below Liebert XDC unit. |
| 8 | |||
8. Do not run piping or wiring in the path of air flow | |||||
| a. Insulated storage receiver - storage | ||||
as this will hamper the system performance. |
|
| |||
|
| receiver (1) per circuit. Receiver size varies. | |||
9. Install |
|
| |||
|
| b. Dual head pressure control valve assembly | |||
gas lines between condenser and field piping. |
|
| |||
|
| with integral check valve(s) - (1) one per circuit (S | |||
10. All other piping |
| ||||
| c. Rotalock valve - (1) one per circuit, | ||||
11. Inverted traps must be installed to allow proper |
|
| |||
|
| d. Pressure relief valve - (1) one per circuit, | |||
clearance to fully open condenser control box door |
| ||||
| e. Liquid level indicator - (1) per circuit | ||||
and in accordance with local electric codes. |
|
| |||
12. Secure |
|
| |||
condenser frame using hardware provided. Receiver |
| DPN000937 | |||
can be mounted on either side of condenser. |
|
| |||
|
| Pg. 02, Rev. 09 | |||
13. |
|
| |||
|
|
| |||
assembly shipped loose for field installation. |
|
|
| ||
Item C is shipped loose for field installation. |
|
|
| ||
14. Fasten liquid and hot gas lines using flat |
| See Figure 29 for details on piping connections. | |||
surface clamps with isolators (field provided). |
|
Support field piping separately to avoid coil damage and loss of charge.
15.Relieve pressure at access port. Replace access port fitting with relief valve before charging system.
25