Specifications
Table 26 Floor stand
Models - 60 Hz |
| XDC160 Water Floor Stand - 60Hz |
| ||
Entering Fluid Temp °F (C) | 65 (18) | 70 (21) | 75 (24) | 85 (29) | 95 (35) |
|
|
|
|
|
|
Performance Data |
|
|
|
|
|
|
|
|
|
|
|
Cooling capacity, tons (kW) | 46.1(162.3) | 46.1(162.3) | 46.1(162.3) | 46.1(162.3) | 44.5 (156.5) |
|
|
|
|
|
|
Flow, GPM | 50 | 58 | 70 | 110 | 142 |
|
|
|
|
|
|
Pressure Drop, psi (Ft Water) | 2.7 (6.2) | 4.9 (11.3) | 5.4 (12.5) | 20.7 (47.8) | 27.3 (63.1) |
|
|
|
|
|
|
Heat Rejection Equipment |
|
|
|
|
|
|
|
|
|
|
|
Water regulating valve size | 1" | 1" | 1" | 1" | 1" |
|
|
|
|
|
|
Piping Connections |
|
|
|
|
|
|
|
|
|
|
|
Water / glycol supply and return lines | |||||
|
|
|
|
|
|
Table 27 Floor stand |
|
Models - 60 Hz | XDC160 Glycol Floor Stand - 60Hz - 40% PG | ||||
Outside Ambient °F (°C) | 95 (35) |
| 100 (38) |
| 105 (41) |
|
|
|
|
|
|
Entering Fluid Temp °F (°C) | 110 (43) |
| 110 (43) |
| 110 (43) |
|
|
|
|
|
|
Performance Data |
|
|
|
|
|
Cooling capacity, tons (kW) |
| 42.5 (149.4) |
| ||
|
|
|
|
| |
Total Heat Rejection, (kW) |
| 192.6 |
|
| |
|
|
|
|
| |
Flow, GPM |
| 206 |
|
| |
|
|
|
| ||
Pressure Drop, psi (ft water) |
| 37.2 (85.9) |
| ||
|
|
|
|
|
|
Heat Rejection Equipment |
|
|
|
|
|
Drycooler | DNT 940A |
| 2 x DNT 880A* | ||
|
|
|
|
| |
Drycooler Pressure Drop, psi (ft water) |
| 6.7 (15.5) |
| 2.9 (6.6) | |
|
|
|
|
|
|
Glycol pump package - 10hp |
|
| 9A31258G3 |
| |
|
|
|
|
| |
Pump Control Package - 208V |
|
| 9A34606G47 |
| |
|
|
|
|
| |
Pump Control Package - 460V |
|
| 9A32114G4 |
| |
|
|
|
|
| |
Pump Total Head @ 204 GPM, ft water |
| 145 |
|
| |
|
|
|
|
| |
Water regulating valve size |
|
|
| ||
|
|
|
|
|
|
Piping Connections |
|
|
|
|
|
Water / glycol supply and return lines |
|
|
| ||
|
|
|
|
|
|
* When multiple drycoolers are used ensure flow is balanced.
55