Lincoln Electric SVM 122-A Input Wire and Fuse Size, Figure A.3 Input Power Supply Connections

Models: SVM 122-A

1 116
Download 116 pages 53.57 Kb
Page 11
Image 11

Return to Section TOC

Section TOC

Return to Master TOC

Master TOC

A-5

A-5

INSTALLATION

FIGURE A.3 – INPUT POWER SUPPLY CONNECTIONS

1.INPUT SUPPLY LINE

2.INPUT CONTACTOR CR1

3.RECONNECT PANEL

Return to

Return to Section TOC

Return to

Return to Master TOC

Have a qualified electrician connect the input power leads to the L1, L2, and L3 terminals of the input con- tactor. Follow all national and local electrical codes. Use a three-phase line. Refer to the connection dia- gram located on the inside cover of the access panel cover. Also see Figure A.3.

INPUT WIRE AND FUSE SIZE

Fuse the input circuit with the super lag fuses recom- mended on the Technical Specifications page or use delay type circuit breakers. Choose an input and grounding wire size according to local or national codes; also see the Technical Specifications page. Using fuses or circuit breakers smaller than recom- mended may result in “nuisance” shut-offs from welder inrush currents, even if you are not welding at high currents.

Return to Section TOC

Return to Master TOC

IDEALARC DC-400

LINCOLN ®

ELECTRIC

Page 11
Image 11
Lincoln Electric SVM 122-A service manual Input Wire and Fuse Size, Figure A.3 Input Power Supply Connections