236 MG 1000B platform hardware installation
Do not modify or use the supplied AC power cord if it is not
the correct type. Refer to in Communication Server 1000S:
Installation and Configuration (NN43031-310) for a detailed
power cord description.
b. Attach the female end of the power cord to the mating AC power
receptacle on the left side of the Signaling Server’s back panel.
See Figure 82 "Back of Signaling Server" (page 235). Plug the
male end of the AC power cordinto the AC power source (wall
outlet).
4Connect a maintenance terminal to the Signaling Server.
a. Connect a DTE–DTE null modem serial cable (supplied with
the Signaling Server) from the back of the Signaling Server to a
maintenance terminal. The connection looks like that shown in
Figure 83 "Maintenance to Signaling Server connection" (page
236).
Figure 83
Maintenance to Signaling Server connection
b. The COM port on the maintenance terminal is set as follows:
Terminaltype: VT100
Speed: 96 000
Data bits: 8
Parity: none
Stop bits: 1
Flow control: none
The Signaling Server is shipped with the Admin/Serial port set
to 19 200 Bit/s. Other available speeds are 38 400, and 115
200 Bit/s.
5Power up the Signaling Server.
a. Open the bezel door (Figure 84 "Signaling Server with open
bezel door" (page 237)) to access the Power switch:
1. Grasp the tab at each end of the hinged bezel door.
Nortel Communication Server 1000
Branch Office Installation and Commissioning
NN43001-314 01.02 Standard
Release 5.0 20 June 2007
Copyright© 2007, Nor tel Networks
.